45
MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
ENGLISH
12. TECHNICAL SPECIFICATIONS
Number of modules
1
2
3
4
5
6
7
8
Power
kW
25
50
75
100
125
150
175
200
Power
kVA
Input
Input mains voltage
3ph + N 340 V to 480 V (+20/-15%) up to -40% @ 50% of nominal load
Input mains frequency
Hz
50/60 +/-10%
Input power factor
≥ 0.99
(1)
Total harmonic input current distortion (THDi)
≤ 3% (@: Pn, Resistive load, Mains THDv ≤ 1%)
Output
Output voltage (three phase + neutral)
V
380/400/415
(2)
selectable
Frequency
Hz
50/60 selectable
Total output voltage distortion (THDv)
%
≤ 1% (Ph/Ph); ≤ 2% (Ph/N) (@: Pn, Resistive load)
Overload
(3)
• 10 min
• 5 min
• 1 min
• 30 s
kW
27,5
31,3
33,8
37,5
55,0
62,5
67,5
75,0
82,5
93,8
101,3
112,5
110,0
125,0
135,0
150,0
137,5
156,3
168,8
187,5
165,0
187,5
202,5
225,0
192,5
218,8
236,3
262,5
220,0
250,0
270,0
300,0
Crest Factor
≥ 2.7
Bypass
Bypass input voltage
V
Nominal output voltage ±15% (±20% if GENSET is used)
Bypass input frequency
Hz
50/60 +/-2% selectable (±8% if GENSET is used)
Stored energy mode of operation
Number of battery blocks (VRLA)
From 18+18 to 24+24
Environmental
Operating temperature
°C
0 to 40 °C
(4)(5)
Storage temperature
°C
-5 to +50 °C
Relative humidity
%
95% condensation-free
Altitude (max)
m
1000 ( 3000 with derating)
Acoustic noise at 1m
dBA
52
52
55
55
55
56
58
58
Required cooling capacity
m
3
/h
400 800 1200
1600
2000
2400
2800
3200
Dissipated power (max)
W
1500
3000
4500
6000
7500
9000
10500
12000
Dissipated power (max)
BTU/h
5120
10240
15360
20480
25600
30720
35840
40960
Dimensions and Weight
Dimensions (W x D x H)
mm
600 x 890 x 1975
Empty cabinet
kg
228
UPS module
kg
33
Bypass module
kg
25
Standard
Safety
IEC 62040-1
EMC
IEC 62040-2 (C2)
Performance
IEC 62040-3 (VFI-SS-111)
Product Certifications
CE – TUV SÜD
Degree of protection standard
IP20
1. Pout ≥ 50% Sn.
2. 360 V with Pout = 90% Pn.
3. Initial Condition Pout ≤ 80% Pn
4. For best battery lifetime the suggested temperature range is 15 °C ÷ 25 °C.
5. According to EN62040-3