40
MODULYS GP Green Power 2.0
range from 25 to 200 kVA - Ref.: IOMMODGPXX05-GB 01
SWITCHING ON FROM MAINTENANCE BYPASS
• Put switch
Q1
(or the external input mains switching device) into position
1
.
• Wait for the display to switch on.
• Enter menu
MAIN MENU > COMMANDS > UPS PROCEDURES
.
• Select
Automatic Start Procedure
and press
ENTER
.
• Carry out the operations indicated on the display.
NOTE!
When an external manual bypass
(1)
is present, put the switch to position 0 (OFF).
1. Not monitored by the UPS or by the parallel system.
8.4. EXTENDED OUT OF SERVICE
When the UPS is deactivated for some time, the batteries must be recharged regularly.
They have to be recharged every three months.
• Connect the mains and auxiliary mains to the UPS.
• Put switch
Q1
into position
1
.
• Wait for the display to switch on.
• Close the external battery breaker/fuses.
• Put or keep switch
Q6
/
Q5
in position
0
.
• The battery must be charged for at least ten hours.
• Once ten hours have elapsed, open the external battery breaker/fuses.
• Put switch
Q1
into position
0
.
8.5. EMERGENCY
SHUTDOWN
NOTE!
This operations interrupts the supply to the output load from both inverters and automatic bypass.
UPS POWER OFF
- System with manual bypass and input, aux mains, output switches: put
Q6
to position
0
when it’s necessary to interrupt the
power supply quickly. Refer to figure 8.5-1.
- System with manual bypass and output switch: push the electronic ‘UPS Power Off’ button when it is necessary to interrupt the
power supply quickly. Refer to figure 8.5-2.
8. OPERATING PROCEDURES
8.5-1
8.5-2
REMOTE UPS POWER OFF
It is possible to interrupt the power supply to the output load using the ADC board. Refer to ‘Standard features and options’ chapter.