8. OPERATING PROCEDURES
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
NOTE!
With the stop procedure the load will be disconnected.
8.1. SWITCHING
ON
• Connect the mains and auxiliary mains to the UPS.
• Put switch
Q1
(or the external input mains switching device) into position
1
.
• Wait for the display to switch on.
• Enter
MAIN MENU > COMMANDS > UPS PROCEDURES
.
• Select
Automatic Start Procedure
and press
ENTER
.
• Carry out the operations indicated on the display.
8.2. SWITCHING
OFF
This operation interrupts the power supply to the load The UPS and the battery charger will be shutdown.
• Enter menu
MAIN MENU > COMMANDS > UPS PROCEDURES
.
• Select
Automatic Stop Procedure
and press
ENTER
.
• Wait approx. 2 minutes for the UPS shutdown.
NOTE!
The controlled shutdown of each server connected to the LAN can be managed by shutdown software.
• Carry out the operations indicated on the display. This operation cannot be aborted.
8.3. BYPASS
OPERATIONS
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part. This operation
is performed in the event of:
- standard maintenance
- serious failure has occurred.
WARNING! LOAD POWERED BY INPUT MAINS!
Your load is exposed to mains disturbances.
• Enter menu
MAIN MENU > COMMANDS > UPS PROCEDURES
.
• Select
ON MAINT. BYPASS
and press
ENTER
.
• Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- put the switch to position 1.