51
EN
ISOM DIGIWARE - 546780C - SOCOMEC
8.
STATUS LEDS, BUTTONS AND AUTO-ADDRESSING
8.1. Status LEDs and buttons
These LEDs can be used to find out the status of the product at any time. Use specific buttons to go straight to the
devices' main functions.
8 .1 .1 . L-60
ON
INJ
FAULT
ALARM 1
RESET
TEST
INJ
START/STOP
ALARM 2
COM
FE
14
11 12
1
C
Output
C
Input
2
3
4
22
24
21
Alarm2
Alarm1
L1
L2
DIGIWARE BUS
θ >
L-60t
ISOM
KE
Power supply (green)
Insulation alert ALARM1
Insulation alert ALARM2
Manual RESET button
Manual test button
(TEST)
Status LED for FLD booster (INJ)
Manual boost START/
STOP button: this button
is mainly used in the
portable locating phase.
It is prioritised in Settings
mode (see § 10.1.2)
System fault (red)
Communication (amber)
Addressing button
LED state
Fixed
Blinking
Pulse
ON
In operation
The screen communicates with
the device to retrieve the values/
data to display.
10 seconds – on request by
a Modbus control command
to identify the device (remote
screen…)
1 second to start-up
FAULT
An alarm (logical/analogue) is
active (does not take priority if
there is a setup alarm at the same
time)
At least one startup alarm is
active.
1 second to start-up
COM
Addressing problem.
Address OK
1 second to start-up and when a
frame received is processed
ALARM 1
Alarm sent when lowest threshold
is not met – ALARM1
ALARM 2
Alarm sent when lowest threshold
is not met – ALARM2
INJ
Injection in fault-locating mode
is ON
When the device is in manual test
mode