8. 9. U
nit
E
nabLEd
c
ontroLs
t
abLE
:
a
ddrEss
0
x
1150; 1 w
ords
code
description
Bit
address
Remarks
v007
Eco-mode
7
0x1150
v008
Normal-mode
8
v032
Unit Start procedure
0
0x1152
v033
Reserved
1
v034
make unit available
2
v035
Switch load to inverter
3
v036
Switch load to mains
4
v037
Switch off unit output
5
v038
6
v039
7
v040
Rectifier on
8
v041
Rectifier off
9
v042
inverter on
10
v043
inverter off
11
v044
12
v045
Battery test
13
8. 10. c
ontroLs
s
End
t
o
U
Ps
: a
ddrEss
0
x
1190,
writE
1
words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using ADICOM interface.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored. Controls available by MODBUS connection:
code
description
Bit to write
address
Remarks
c007
Eco-mode
7
0x1190
c008
Normal-mode
8
c032
Unit Start procedure
0
0x1192
c033
Reserved
1
c034
make unit available
2
c035
Switch load to inverter
3
c036
Switch load to mains
4
c037
Switch off unit output
5
load oFF immediate!!
c038
6
c039
7
c040
Rectifier on
8
c041
Rectifier off
9
c042
inverter on
10
c043
inverter off
11
c044
12
c045
Battery test
13
c046
14
c047
c048
reset alarm
0
0x1193
s
Ingle
UnIt
UPs m
odbUs
t
ables
20
Delphys green power
- Ref.: IOMDGPJB0910-GB_11