5. 4. c
onnEctions
and
wiring
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
5. 4.1. RS232 connection:
–
Standard PC connection
–
Sub-D 9 pins connector
–
Pin 2 :
Rx
–
Pin 3 :
Tx
–
Pin 5 :
Gnd
5. 4.2. Isolated RS485 connection
–
2 wires connection
–
« dip-switch 1 » allows connecting the terminal resistor
–
Insulation via “opto-coupler”
–
2 polarization resistors could be removed easily (if needed).
5. 4.3. Isolated RS422 connection
–
4 wires connection
–
« dip-switch 1 and 2 » allows connecting the terminal
resistor
–
Insulation via “opto-coupler”
–
4 polarization resistors could be removed easily (if needed).
RTX + RTX -
TX -
RX -
TX +
RX +
Before making any connection, please check the cabling. A wrong connection or cabling can damage
the serial link interface.
the shield should be earthing at one point.
the shield should be earthing at one point.
I
nstallatIon
I
nsIde
UPs
7
Delphys green power
- Ref.: IOMDGPJB0910-GB_11
ENGLISH