8. 6. U
nit
s
tatUs
: a
ddrEss
0
x
1143, 4 w
ords
code
description
Bit
address
Remarks
S048
Load on inverter
0
0x1143
S049
Load on auto. Bypass
1
S050
Load on maintenance Bypass
2
S051
Load not supplied
3
S052
unit is available
4
S053
Unit isolated from inst.
5
S054
Output switch Q2/3 closed
6
S055
Rectifier ON
7
S056
Battery charging
8
S057
Battery charged
9
S058
10
S059
inverter on
11
S060
Inverter switch/contactor closed
12
S061
Bypass switch activated
13
S062
14
S063
Servicing alert
15
S064
Rectifier input supply fault
0
0x1144
S065
Bypass input supply out of tolerance
1
S066
Bypass input supply failure V/F 2
2
S067
Bypass input supply is synchro ref
3
S068
Ext. synchro ref (ACS on)
4
S069
Synchro forced on ACS
5
S070
“UPS general power off” input active
6
S071
Generator set active
7
S072
Unit in normal mode
8
S073
Unit in eco-mode
9
S074
10
S075
Unit in stand-by mode
11
S076
12
S077
13
S078
14
S079
Unit in servicing mode
15
s
Ingle
UnIt
UPs m
odbUs
t
ables
14
Delphys green power
- Ref.: IOMDGPJB0910-GB_11