13. 2. modbUs tcP ida
sPEcification
The JBUS frames below are only examples:
REQUEST BY MASTER IN MODE JBUS/MODBUS RTU
Original frame:
01 03 1034 0003 40C5
Encapsulated frame:
0046 0000 0006 01 03 1034 0003
where:
0046
corresponds to the transaction number
0000
corresponds to the protocol identifier
0006
corresponds to the number of bytes (length of the message)
note:
The CRC is suppressed in the encapsulated MODBUS frame.
REPLY OF THE UPS IN MODE JBUS/MODBUS RTU:
Original frame:
01 03 06 0002 0184 0000 1960
Encapsulated frame:
0046 0000 0009 01 03 06 0002 0184 0000
where:
0046
corresponds to the transaction number
0000
corresponds to the protocol identifier
0006
corresponds to the number of bytes (length of the message)
Note: The CRC is suppressed in the encapsulated MODBUS frame.
ANNEXE
46
Delphys green power
- Ref.: IOMDGPJB0910-GB_11