8. 3. U
Ps
i
dEntification
: a
ddrEss
0
x
1100, 32 w
ords
code
description
number
address
type
Remarks
i000
UPS identification
10 wordS
0x1100
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
i010
UPS Description
6 wordS
0x110A
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
i016
Location
6 wordS
0x1110
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
i022
Serial number
10 wordS
0x1116
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
8. 4. d
atE
& H
oUrs
: a
ddrEss
0
x
1360, 4 w
ords
code
description
number
address
type
Remarks
d00
Minutes / seconds
1 wordS
0x1360
Byte value
MSB = minutes, LSB = seconds
d01
Hours / day
1 wordS
0x1361
Byte value
MSB = day, LSB = hours
d02
Month / day of
week
1 wordS
0x1362
Byte value
MSB = month,
LSB = day of the week
1=Monday...7=Sunday
d03
year
1 wordS
0x1363
00 = 2000
8. 5. U
Ps
c
onfigUration
: a
ddrEss
0
x
1120, 16 w
ords
code
measurements
unit
address
Remarks
t000
Kind of equipment
0x1120
1= single unit, 3= pa centralised bypass
6 = modular parallel system
t001 uPS output power
kva
0x1121
t002 unit output power
kva
0x1122
t003 unit number
0x1123
1 - 8
t004 number of unit
0x1124
1 - 8
t005
UPS redundant
0x1125
0 - 1
t006 with battery
0x1126
0 - 1
t007
With flywheel
0x1127
0 - 1
t008
0x1128
t009
With genset
0x1129
0 - 1
t010
0x112A
t011
0x112B
t012
0x112C
t013
With rectifier input supply
0x112D
0 - 1
t014
Single
0x112E 0 = Tri, 1 = Single
t015
Measurements management
0x112F
0 = x 1, 1 = x 10
s
Ingle
UnIt
UPs
modbUs
tables
13
Delphys green power
- Ref.: IOMDGPJB0910-GB_11
ENGLISH
Summary of Contents for DELPHYS BC
Page 47: ......