compliaNcE
european eMc Directive no. 2004/108/ec (15/12/2004)
lv Directive no. 2006/95/ec Dated 12 December 2006
MiD Directive 2004/22/ec
en50470-1/-3 (february 2007)
SyStEm coNNEctioN
Supply types / number of wires
Single phase 2 wires 230v / two phase 2 wires 400v
three phase 3 wires 3x230 v / 3x400 v and three phase 4 wires
3x230/400 v
Management
Detection of cabling error
frequency
50 (+/- 1 Hz)
Supply
autosupplied
coNSumptioN
Supply
< 10 va or 2 W
current circuit
< 1.0 va
currENt (trmS)
Starting current (ist)
5 ma
Minimum current (imin)
50 ma
transition current (itr)
250 ma
reference current (iref)
5 a
Permanent overload (imax)
6 a
Short-term over-current
120 a for 0.5 s (en50470-3 and iec 62053-21)
VoltagE (trmS)
Direct measurement
230 v ac Phase/neutral 400 v ac Phase/Phase +/- 15%
Permanent overload
230 / 400 v ac +/- 15%
poWErS
active yes
reactive no
resolution
0.1 kW
ENErgy
active yes
reactive yes
total and partial metering
no (0 to 999999.9 kWh)
Bidirectional metering (ea+ and ea-)
no
resolution
1 kWh
prEciSioN
active energy
class c (en 50470-3)
tariffS
tariff management
yes
number of tariffs managed
2
tariff exchange input
yes
mEtrological lED
impulse weight
10000 impulses / kWh
colour red
DiSplay
type
7 Digit leD with blue back-lighting
refresh time
1 s
Back-lighting illumination time
30 s
list of functions displayed
cf. table below
GB
46
COUNTIS E42
- Ref.: 537 378 A
CARACTéRISTIQuES TEChNIQuES
TEChNICAl ChARACTERISTICS - TEChNISChE DATEN - CARATTERISTIChE TECNIChE -
TEChNISChE kENMERkEN - CARACTERíSTICAS TéCNICAS - CARACTERíSTICAS TéCNICAS
Summary of Contents for COUNTIS E42
Page 17: ...17 COUNTIS E42 Fig 1 Fig 2...
Page 19: ...Fig 1 Fig 2 19 COUNTIS E42...
Page 21: ...Fig 1 Fig 2 21 COUNTIS E42...
Page 23: ...Fig 1 Fig 2 23 COUNTIS E42...
Page 58: ...58 COUNTIS E42 Ref 537 378 A...
Page 59: ...59 COUNTIS E42...