Mode Breaker (preferred control method for ATyS dH)
Wiring diagram to be utilised when ATyS C55/C65 configured for “SWITCH TECHNOLOGY” as “BREAKER”
CAUTION !
- The ATyS C55/C65 must be configured to stop in the “0 position” (DEAD BAND TIMER) for a duration that
is set higher than that as set on the transfer switch. (Minimum setting value 2s).
- DEAD BAND TIMER value of the ATyS C55/C65 controller must be higher than [1FT + 2AT] timers value :
1FT + 2AT ≤ DBT.
1FT – Source 1 failure timer
2AT – Source 2 availability timer
DBT – Dead Band Timer
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
USB
CT
IN1 IN2 IN3 IN4 IN5 IN6COM
RS485
SOURCE 1
DIGIWARE
DIGIWARE
INPUTS
SOURCE 2
11 14 12
21 24 22
31 34 32
41 44 42
51 54 52
61 64 62
71 72 73 74 75 76 70 82 81
L1 L2 L3 N
NC
+
L2 L3 N
L1
-
I1 I2 I3 IN GNDGND
UTILISATION
CN AC2 BC2 AT2 BT2
ATyS d H
A1 A2 CP AC1 BC1 AT1 BT1
22 21 14 11 34 31 41 42 B2 B1
L1
L2
L3
1
N
L1
L2
L3
N
2
F2
F1
F3
F4
F1, F2
Protection fusible s
230 Vac 5 A
F3, F4
Protection fusible s
230 Vac 32 A