14
EN
ATyS d H - 544077E - SOCOMEC
5.4.
Power circuits and bar connections
4000 A
AC-32B
AC-33iB
PC
PC
IEC
60947-6-1
GB
14048.11
4000 A
AC 230 V 50/60 Hz AC 220 V 50 Hz
Fixed
3
4000 A
65 A
65 A
65 A
65 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
660 V 50 Hz
660 V 50/60 Hz
AC-32B
AC-33iB
PC
PC
IEC
60947-6-1
GB
14048.11
4000 A
AC 230 V 50/60 Hz AC 220 V 50 Hz
Fixed
4
4000 A
65 A
65 A
65 A
65 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
660 V 50 Hz
660 V 50/60 Hz
4000 A
4000 A
AC-32B
AC-33iB
PC
PC
IEC
60947-6-1
GB
14048.11
4000 A
AC 230 V 50/60 Hz AC 220 V 50 Hz
Draw out
3
4000 A
65 A
65 A
65 A
65 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
660 V 50 Hz
660 V 50/60 Hz
AC-32B
AC-33iB
PC
PC
IEC
60947-6-1
GB
14048.11
4000 A
AC 230 V 50/60 Hz AC 220 V 50 Hz
Draw out
4
4000 A
65 A
65 A
65 A
65 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
660 V 50 Hz
660 V 50/60 Hz
4000 A
Ref.95333400
Ref.95333401
Ref.95334401
Ref.95334400
Recommended tightening torque:
4000A: M12 / 45 Nm
5000A: M12 / 45 Nm
6300A: M12 / 45 Nm
Maximum tightening torque:
4000A: M12 / 45 Nm
5000A: M12 / 45 Nm
6300A: M12 / 45 Nm
Note: terminals RR, SS, TT and NN are each to be connected in parallel and must be bridged as shown above.
Bridging bars are not included with the product and must be supplied by others.
5.5.
Busbar connection recommandations
Rating
Cross section per bar
Quantity of bars per phase Type of screw
Recommended tightening torque (N.m)
4000 A
100mm x 10mm
4
M12
45Nm
5000 A
100mm x 10mm
5
M12
45Nm
6300 A
100mm x 10mm
6
M12
45Nm