ANNEX NXP Release 7.1 dated 19-02-2018
3
If more RELAY output are necessary for application, option board NXOPTB5, equipped with 3 output relays
with 125Vdc 0,4A contact, can be used.
The RO1, RO2 and RO3 relays can be programmed as any digital output, through the following parameters
(in the column “Default” the SMS setting is shown).
Par.
Description
u.d.m.
Default
Value
P2.7.7.1
Config uscitaOptR01 / Opt R01 Content
15 / Motor Switch
P2.7.7.2
Config uscitaOptR02 / Opt R02 Content
16 / MotSwitDelay
P2.7.7.3
Config uscitaOptR03 / Opt R03 Content
s
11 / Freq Supervis
P2.7.7.4
LimiteVerif Freq / Freq Superv Limit
1 / Low Limit
P2.7.7.5
ValueVerif Freq / Freq Superv Value
Hz
30
ANALOG OUTPUT
By means of parameter P2.7.6.1, the analog output (term. 18-19 – 20mA-10V) can be programmed to
several inverter values:
Output frequency Hz
1
Motor frequency
Frequency reference Hz
2
Frequency settled with parameters
Motor speed rpm
3
Calculated motor speed
Motor current Amps
4
Measured motor current
Motor torque %
5
Calculated torque / nominal motor torque
Motor power %
6
Calculated power / nominal motor power
Motor voltage V
7
Calculated motor voltage
DC link voltage V
8
Measured DC link voltage
Encoder speed rpm
9
Speed measured from encoder (real motor speed)
In addition, it can be programmed as digital output, following the table below:
Motor Switch
10
Motor Contactor switch-off command
(0.3 seconds after the inverter switch-off).
Motor Switch Delayed
11
The output copies the motor switch control, but it goes off
delayed 2 more seconds.
Brake Command
12
It copies the RO2 output status (NXOPTA2 Board),
you must use this output to control the BRAKE through the
NXBR1 option board.
Ropes to be replaced
13
If the output switches on, it means that the counter
measuring the cable bending cycles has reached the 0
value.
If the ANALOG OUTPUT is connected to a relay, this one must have a
12Vdc coil - 500
Ω
MAX
.
Summary of Contents for TAKEDO-3VF
Page 8: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 8 INTENTIONALLY BLANK PAGE ...
Page 28: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 28 ASYNCHRONOUS MOTORS CLOSED LOOP ...
Page 50: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 50 ...
Page 58: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 8 ...
Page 59: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 9 ...