TAKEDO - 3VF NXP USER MANUAL Release P09.1 dated 01-12-2017
19
Alarm 68 NOTE
After 20 trips of this alarm, the drive goes out of service and you need to use RESET key
to resume the operation.
To check the total amount of the Alarm 68 trips, please see the Menu
M1 MONITOR – V1.1.10.
Eliminate the malfunction by delaying director command and hence also contactor
opening. If you can’t do this (for example, in lifts with manual doors, where people open
the car door once the car has stopped), set parameters P2.3.1.5 and P2.3.1.2 to 0.
If the fault persists, please contact SMS ..
EARLY OPENING OF MOTOR CONTACTOR SHORTENS INVERTER LIFE. INVERTER
LIFE
5.5 M5 = FAULT HISTORY
The caption H1
→
Hx appears under the menu. This indicates how many faults are memorized. Up to 30
faults can be memorized and displayed chronologically in reverse order (most recent fault displayed first).
Pressing the key when viewing the fault code opens the "Instant fault data register", in which the values
of several key variables are saved (e.g. output frequency, motor current, motor torque, etc.) as they occur.
Press the or keys to scroll this register.
To reset faults, the (ENTER) key must be pressed and held for at least 3 seconds.
5.6 M6 = SYSTEM MENU
The caption S1
→
Sn appears under the menu. This means there are “n” submenus.
S6.1 Language Setting:
ITALIAN / ENGLISH / FRENCH / GERMAN.
S6.2
Application Setting:
AsynchMotor / PermMagnSync
SMS advises against modifying other parameters relative to this MENU.
If necessary, contact SMS or use the original manual available at www.vacon.com.
5.7 M7 = EXPANDER BOARDS
The caption G1
→
Gn appears under the menu. This means there can be up to “n” submenus. The number of
submenus depends on the number of optional circuit boards connected.
G7.1 NXOPTA1 G1
→
→
→
→
G2 (Board on Slot A)
SMS advises against modifying the parameters relative to this submenu.
G7.2 NXOPTA2 G1
→
→
→
→
G1 (No. 2 digital relay outputs, slot B)
G7.2.1 I/O monitor V1
→
→
→
→
V2
Parameter Description
UM
Def.
Value
V7.2.1.1
DigOUT:B1 (Digital output B.1)
-
V7.2.1.2
DigOUT:B2 (Digital output B.2)
-
G7.2 NXOPTA3 G1
→
→
→
→
G1 (No. 2 digital relay o No. 1 input, slot B)
G7.2.1 Monitor I/O V1
→
→
→
→
V3
Par.
Description
m. u.
Def.
Value
V7.2.1.1
DigIN:B1 (Inlet B.1)
-
V7.2.1.2
DigOUT:B1 (Digital output B.1)
-
V7.2.1.3
DigOUT:B2 (Digital output B.2)
G7.4 NXOPTB5 G1
→
→
→
→
G1 (No. 3 digital relay outputs, slot D) (OPTIONAL)
G7.3.1 I/O Monitor V1
→
→
→
→
V3
Par.
Descrizione
u.d.m.
Def.
Valore
V7.4.1.1
DigOUT:D1 (Digital output D.1)
-
V7.4.1.2
DigOUT:D2 (Digital output D.2)
-
V7.4.1.3
DigOUT:D3 (Digital output D.3)
-
Menus for ENCODER boards are illustrated in the section on CLOSED LOOP application and for
SYNCHRONOUS MOTORS.
enter
Summary of Contents for TAKEDO-3VF
Page 8: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 8 INTENTIONALLY BLANK PAGE ...
Page 28: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 28 ASYNCHRONOUS MOTORS CLOSED LOOP ...
Page 50: ...TAKEDO 3VF NXP USER MANUAL Release P09 1 dated 01 12 2017 50 ...
Page 58: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 8 ...
Page 59: ...TAKEDO 3VF NXP Attachment for A3 Amendment Version 03 1 dated 01 12 17 9 ...