RED-G
38
REV. 9 PRINTED 02/2018
CHECK AND MAINTENANCE
In any case of electric check or modification,
please be sure to open IE switch and to disconnect the mains power.
Verify periodically what follows, starting with mains voltage present:
1) Check that there is no oxidation on the battery terminals
2) Check each battery charger measuring the output voltage (54VDC) and the status of
Green and Red leds on the BACH Board (only green led must be lighted ON).
3) Switching OFF the mains power with 4thpole open, the rescue operation MUST NOT to
start.
4) Closing the 4th pole with a bridge, rescue operation has to start and finish properly,
please follow indications at Chapter 7 – COMMISSIONING – points 7) ÷ 10).
If rescue operation doesn’t properly end and RGCON board indicates ‘Wrong Battery
Voltage’, batteries may have to be replaced. Remove the bridge done on the 4thpole .
5) After some years of work, typically 4, replace the batteries and apply a label indicating
the date of replacement.
SPARE PART LIST
DESCRIPTION
SMS CODE
RED-G 3000
RED-G 4000
RED-G 8000
CONTACTORS KE1 – KE2 24Vdc
003.07.AB250
003.07.AB400
3-PHASE INDUCTANCE
003.11.0500200M
50A
003.11.0200700M
20A
3-PHASE TRANSFORMER
003.08.B0035
2kVA
003.08.B0037
4kVA
003.08.B0039
8kVA
AUTOMATIC SWITCH 63A
003.12.1X063
003.12.1X063C
with auxiliary
module
003.12.AUX11
FAN 24VDC 80x80x25
003.19.00005C
BATTERY CHARGER 48V 2,5A
202.06.BACH1.48
LOGIC BOARD
202.06.RGCON1
(or next rel.)
POWER BOARD
202.06.RGMOS2
(or next rel.)
CAPACITORS 450Vac
004.05.M0630
30uF
004.05.MX510
1uF
004.05.MX550
5uF
C
HECK
AND
M
AINTENANCE
/ S
PARE
P
ART
L
IST