Issue 001 - November 2018 | SmithsEP.co.uk | 17
How it works - Heater
Cooler air is drawn in by the fan and heated as it
passes through the heating element before being
discharged gently back into the room. This not
only gives a more even temperature spread, but
will heat up a room quicker than a traditional
panel radiator.
Cold air in
Warm air out
Cold air in
temperature
adjustment
buttons
temperature
display screen
ON/OFF
button
Batteries in Wall Controller
Is recommended that the battery is changed
every 12 months to protect potential damage by
batteries leaking (batteries are supplied with the
controller)
You do not need to re-pair after batteries have
been changed (pairing is done by programming
the chip memory)
Wall Controller
Introduction
In compliance with LOT20 European legislation,
this product is supplied with a wireless battery
powered wall-mounted time and temperature
controller. The product will NOT function without
the wall-mounted controller. The controller can
control an unlimited number of heaters.
The controller is primarily designed to minimise
energy wastage and ensure the room is
maintained at the comfort level set by the user.
In the basic setting, the controller is a simple
room thermostat in which the heater will run
until the set temperature is reached. If the room
temperatures falls the heater will switch on again
until the set temperature is reached.
The operating range is between 15°C and 35°C.
The controller has a number of advanced
features that, if required MUST be set during
the installation process. Please discuss with your
customer which features they require. The dip
switches will need to be set prior to attaching the
thermostat to the back box.
•
Temperature control for Comfort (COMF)
This can be set to limit the maximum
temperature set by the user.
•
Temperature control for Setback (SETB)
This can be used for frost protection or situations
where a minimum room temperature must be
maintained. The setback temperature can be set
between 0°C and 15°C.
•
Run-back Timer
This can be used to limit the run time of the
heater from between 5 minutes and 2 hours.
The Run-back Timer cannot used be used in
conjunction with Temperature control for
Setback (SETB).