2. Isolate the electrical supply and connect the
heater electric cable to the 10A fused spur.
The fused spur must not be directly above the
heater, but should be accessible after
completion of the installation.
3. Position the heater, making sure the electrical
cable is not snagged.
4b. If required fit the overlay grille. Remove the
screws holding the fixed grille to the plinth,
place the overlay grille over the fixed grille
and refit the screws.
1
Turn on the electrical supply at the fused spur.
2
Set any room thermostat/s to maximum.
3
Set the upper fan switch to ON — the fan will run.
4
Set the middle 1kW switch to ON — heat will
flow immediately (1kW).
Commissioning
5
Set the lower 2kW switch to ON — additional
heat will flow (2kW).
6
When the installation is working correctly,
remember to reset any room thermostat/s to
its normal setting.
GRILLE TO PLINTH SECURING SCREWS
Fault Finding
In the event of any difficulty, please contact us on 01245 324560.
1. Fan does not run/no heat output.
a. Check the power supply is switched ON.
b. Check fuse in the fused spur.
c. Check the fan switch is ON.
2. If the overheat protection has activated,
a. Switch the power supply OFF at the fused spur.
manually reset as follows.
b. Wait five minutes for the overheat cut out
switch to reset.
c. Switch the power supply ON.
4a. Fix heater to the plinth.
17