- 44 -
(2) READY
1 (ON) appears when the gateway is activated.
(3) ALARM
1 (ON) appears when one or more abnormal station are present, and the alarm is generated. 0 (OFF)
appears when alarm is not generated.
(4) Initial
0 (OFF) appears during processing the initial for check the connect station. 1 (ON) appears when the
processing of the initial is completed.
(5) During communication
1(ON) appears when communication is made for one or more station. 0 (OFF) appears when not
communicated.
In one of following cases, communication is not made.
CN2SW is ON.
Stop[InputAddress0.7] is ON.
All the connect stations become abnormal and the communication is stopped.
(6) Return of the read numerical data (Valid only in numerical data input mode)
ON (1) appears in ID bit if numerical data can be read. OFF (0) appears when the data can not be read.
The command to read numerical data is given by “Setting numerical data”.
I_Address
bit
7
6
5
4
3
2
1
0
1 -
-
- ID5 ID4 ID3 ID2 ID1
2 -
-
-
-
-
-
-
-
(7) Return of the final station number
Return the range of the ID of the controller (LEC) to communication when the initial is processed. ID
number is returned in binary digit.
ID
bit
3
2
1
0
1
0 0 0 1
2
0 0 1 0
3
0 0 1 1
:
:
5
0 1 0 1