- 8 -
■
Process data
Process data is the cyclic data which is exchanged periodically between the base module and
device.
Process data consists of PD_IN (process data input); 4 BYTE and PD_OUT (process data
output); 2 BYTE as shown below.
-
The process data of this product is Big-Endian type.
When the transmission method of the upper communication is Little-Endian type, the BYTE
order will be changed.
Refer to the table below for the Endian type of the major upper communication.
Endian type
Upper communication protocol
Big-Endian type
PROFIBUS and PROFINET
Little-Endian type
EtherNET/IP, EtherCAT and CC-Link IE Field.
Process data input: 4 BYTE (device (ITV) --> base module)
Bit offset
Item
Note
0
SSC1
Turns ON when the output pressure is /-10%F.S.
of the set pressure.
1 and 2
Disabled
Not used. The value is not reflected.
3
Diagnostic
information
(notification)
0: Normal, 1: Notification (defined per Bit)
*: Refer to the table for Diagnostic information
4 to 10
Diagnostic
information
(warning)
0: Normal, 1: Notification (defined per Bit)
*: Refer to the table for Diagnostic information
11 to 15
Diagnostic
information
(abnormal)
0: Normal, 1: Abnormal (defined per Bit)
*: Refer to the table for Diagnostic information
16 to 31
Output
pressure
No symbol, 16-Bit
*: Refer to the table for Output pressure
Output pressure
Output pressure of the product is sent.
0
1
BYTE
31
30
29 28 27 26 25
24
23
22
21
20
19
18
17 16
Bit
Output pressure
(16Bit)
Value
Monitoring of output pressure
The output pressure can be monitored by the PLC receiving the output data from the regulator
where the output pressure is 13-Bit. (The upper 3 Bit (29th to 31th) are 0).
<Relation between the output pressure value (16-Bit) and output pressure>
Output pressure
0x0000
0x0FFF
Output pressure
0%
100%
Check the values from the 16th to 28th Bit of the 32-Bit (4-BYTE) process data.
(When F_1=0%F.S. and F_2=100%F.S.)
(Ex.) When the output pressure is 100%, the set pressure value is 0x0FFF.