- 10 -
Process data output: 2 BYTE (base module --> device (ITV))
The product adjusts the pressure to the set value.
0
1
BYTE
15
14
13 12 11
10
9
8
7
6
5
4
3
2
1
0
Bit
Set pressure value.
(16Bit)
Value
* Data is adjustable up to 120%F.S. (Max. guaranteed output pressure accuracy is 100%F.S.)
Pressure setting mode
The pressure can be set by sending input data from the base PLC to the regulator where the
full span is 12-Bit. Do not use values outside of the specification range (including Bit 13th to
15th). They are recognized as large values which could cause an error (Er1).
<Relationship between the set pressure (16-Bit) and output pressure>
Set pressure
0x0000
0x0FFF
Output pressure
0%
100%
Input data shall be entered from Bit 0 to Bit 12 of the 16-Bit process data (2 BYTE).
(When F_1=0%F.S. and F_2=100%F.S.)
(Ex.) When the output pressure is 100%, the set pressure value is 0x0FFF.
■
IO-Link parameter setting
●
IODD file
IODD (I/O Device Description) is a definition file which provides all properties and
parameters required for establishing functions and communication of the device.
The IODD includes the main IODD file and a set of image files such as vendor logo, device
picture and device icon.
The IODD file is shown below.
Product
No.
Communication
speed
Process data size
IODD file
※
ITV*0*0
-IL*****
-********
COM3
(230.4 kbps)
4-BYTE input /
2-BYTE output
SMC-ITV-IL-yyyy
㎜
dd-IODD1.1
*
:
yyyymmdd" indicates the file preparation date of the file. yyyy is the year, mm is the month
and dd is the date.