- 11 -
●
Data storage
The data storage function stores the IO-Link device parameter settings to the IO-Link master.
If the index and sub-index of a single parameter of an electro-pneumatic regulator are
specified (changed) and the parameters are uploaded (stored) to the IO-Link base data
storage server, the system command "ParamDownloadStore" of the communication
instruction must be manually sent to the electro-pneumatic regulator for back up.
When the block parameter function of the IO-Link tool is used for setting all parameters in
batch, "ParamDownloadStore" is automatically sent to the system command as part of the
block parameter sequence. The customer does not need to manually issue a system
command.
When the electro-pneumatic regulator is replaced with the same type of regulator, the
parameters stored in the IO-Link base is automatically downloaded to the electro-pneumatic
regulator and the factory settings will be rewritten.
●
Service data
The tables below indicate the parameters which can be read or written by simple access
parameter (direct parameters page) and ISDU parameters which are applicable to various
parameters and commands.
Direct parameters page 1
Address
Access
Parameter name
Default
(decimal number)
0x07
R
Vendor ID
0x0083(131)
0x08
0x09
R
Device ID
0x0219(537)
0x0A
0x0B