No.DIG-31900-OM002
43
(500) Forced fully close/
fully open setting
Forced fully close / fully open is selectable. (on) when the mode is
set. (oFF) when the mode is not selected. When selected, set
value can be changed.
Procedure
LCD display
1
Hold down set button ( ) for
1sec. or longer to start parameter
change mode.
2
Select forceful fully close / fully
open mode (on) or not (oFF) with
Down or Up button ( ).
3
When during the mode is selected,
hold down set button ( ) for
1sec. or longer to start value
change mode. When (oFF) mode is
selected, hold down mode button
( ) for 1sec. or longer to set the
value.
4
<Hereafter, only when (on) is set>
To set lower limit with (510), hold
down set button ( ) for 1sec.
or longer. After values start to flash,
change the value within the range
of 0.0 to 10.0%. After changing,
hold down mode button ( ) to set
the value.
+
or
+
+
or
Upper limit setting
(%)
Lower limit setting
(%)
or
Fig. 36
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Summary of Contents for IP8101 Series
Page 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Page 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Page 75: ...No DIG 31900 OM002 74 Drawing...
Page 76: ...No DIG 31900 OM002 75...
Page 77: ...No DIG 31900 OM002 76...
Page 78: ...No DIG 31900 OM002 77...
Page 79: ...No DIG 31900 OM002 78...
Page 80: ...No DIG 31900 OM002 79...
Page 81: ...No DIG 31900 OM002 80...
Page 82: ...No DIG 31900 OM002 81...
Page 83: ...No DIG 31900 OM002 82...
Page 84: ...No DIG 31900 OM002 83...