No.DIG-31900-OM002
41
Procedure
LCD display
4
<Hereafter, only when (on) is set>
For lower limit setting with (310),
hold down set button (
) for
1sec. or more. After value starts
flashing, change value within the
range of 0.0 to 80.0%. After
changing, hold down mode button
( ) for 1sec. or longer to set the
value.
5
Hold down Down or Up button
( ) for 1sec. or longer. As
setting lower limit in clause 4
above, set the upper limit within the
range of 40.0 to 125.0% with (320).
After changing, hold down mode
button ( ) for 1sec. or longer to set
the value.
6
Hold down the mode button ( ) for
1sec. or longer. Hold down again
for 1sec. or longer after interval.
+
or
Upper limit setting
(%)
or
or
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Lower limit setting
(%)
Fig. 35