No.DIG-31900-OM002
33
(500) Forced fully-close/
fully-open setting
*
6
(600) Dead band setting
Fig. 28
Dead band setting is available. Dead band setting makes the
operation near the target value gentle because the integration
time (I constant) will be cleared, and that makes stability
improved. Dead band can be set in the range between 0.0 and
10.0%. The default value at shipping is 0.0%.
Target value
Dead band (D.B)
0%
S
tr
ok
e
Time
D.B
2
Deviation
The forced fully-closed / fully-open operation can be selected by
setting ON or OFF. The default at shipping is ON. If ON is
selected, the fully-closed setting (510) (input current range
between -0.0 and 10.0%) and the fully-open setting (520) (input
current range between 90.0 to 100.0%) can be set. The default
value at shipping is (510) = 0.5%, and (520) = 99.5%.
95%
(19.2mA)
5%
(4.8mA)
0.5%
100
%
0%
100%
S
tr
ok
e
Input current
(Ex.a) Select (200) = dir when
(510) = 5.0 and (520) = 95.0
0.5%
95%
(19.2mA)
5%
(4.8mA)
100
%
0%
100%
(Ex.b) Select (200) = rvS when
(510) = 5.0, (520) = 95.0
0.5
%
0.5%
S
tr
ok
e
Input current
Fig. 27
The forced fully-close/ fully-open setting will follow the input value
(S value). The position value (P value) will have no influence on
the setting.
6: If forced fully-close/ fully-open is set for a small actuator, it may cause
a very fast actuator movement. In that case, set the forced
fully-close/ fully-open setting at OFF.
Summary of Contents for IP8101 Series
Page 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Page 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Page 75: ...No DIG 31900 OM002 74 Drawing...
Page 76: ...No DIG 31900 OM002 75...
Page 77: ...No DIG 31900 OM002 76...
Page 78: ...No DIG 31900 OM002 77...
Page 79: ...No DIG 31900 OM002 78...
Page 80: ...No DIG 31900 OM002 79...
Page 81: ...No DIG 31900 OM002 80...
Page 82: ...No DIG 31900 OM002 81...
Page 83: ...No DIG 31900 OM002 82...
Page 84: ...No DIG 31900 OM002 83...