No.DIG-31900-OM002
36
(900) Alarm 1 setting
(A00) Alarm 2 setting
Alarm 1 can be selected by setting ON
*
12
or OFF. The default at
shipping is OFF. In addition, an alarm can be selected from the
following with ON selected.
Lower limit alarm (Lo)
Upper limit alarm (UP)
The default value at shipping is the lower limit alarm (Lo). The
alarm (920) (actuator position range between -20.0 to 120.0%)
can be set. The default value at shipping is (920) = 0.0%.
The setting for alarm 1 will follow the position value (P value).
The input value (S value) will have no influence over the setting.
12: When an alarm is output, which will be indicated on a LCD indicator.
See “
■
Contents of LCD D
isplay” for detail.
(910) =
Alarm 2 can be selected by setting ON
*
13
or OFF. The default at
shipping is OFF. In addition, an alarm can be selected from the
following with ON selected.
Lower limit alarm (Lo)
Upper limit alarm (UP)
The default value at shipping is the upper limit alarm (UP). The
alarm (A20) (actuator position range between -20.0 to 120.0%)
can be set. The default value at shipping is (A20) = 100.0%.
The setting for alarm 2 will follow the position value (P value).
The input value (S value) will have no influence over the setting.
13: When an alarm is output, which will be indicated on a LCD indicator.
See “
■
Contents of LCD D
isplay” for detail.
(A10) =
Summary of Contents for IP8101 Series
Page 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Page 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Page 75: ...No DIG 31900 OM002 74 Drawing...
Page 76: ...No DIG 31900 OM002 75...
Page 77: ...No DIG 31900 OM002 76...
Page 78: ...No DIG 31900 OM002 77...
Page 79: ...No DIG 31900 OM002 78...
Page 80: ...No DIG 31900 OM002 79...
Page 81: ...No DIG 31900 OM002 80...
Page 82: ...No DIG 31900 OM002 81...
Page 83: ...No DIG 31900 OM002 82...
Page 84: ...No DIG 31900 OM002 83...