4. Calibration
Automatically perform zero point / span adjustment and PID
constant
*
8
.
Procedure
LCD
1
Press the Down or Up button
( ) in calibration mode to
select calibration (CAL), and press
and hold down the set button
( ) for 1 sec. or longer.
2
The LCD displays go (Go) for
confirmation. Confirm there are no
hazardous conditions due to the
actuator startup, and then press
and hold down the set button
( ) for 1sec. or longer
*
9
.
3
Zero point and span adjustment
begins, and the actuator performs
steps 1 (StP1) to step 3 (StP3)
automatically
*
10
.
4
After the actuator stops, check the
LCD. If it shows good (Good),
calibration the (CAL) mode
selection screen automatically
returns and adjustment is finished.
8: Actuators which take 1 sec. or more per degree after beginning to
move can not normally be provided with span adjustment. Such
actuators cannot be combined with this positioner, and this fact
should be noted.
9: When the button is pressed, the actuator is fully opened or closed, so
avoid touching the actuator or positioner to prevent injuries. Also, the
actuator operates during adjustment and neither it nor the positioner
should be touched until adjustment is completely finished.
10: Adjustment might take up to 2min. Actual time will vary depending
on the actuator capacity.
or
+
+
Warning
!
Summary of Contents for IP8101 Series
Page 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Page 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Page 75: ...No DIG 31900 OM002 74 Drawing...
Page 76: ...No DIG 31900 OM002 75...
Page 77: ...No DIG 31900 OM002 76...
Page 78: ...No DIG 31900 OM002 77...
Page 79: ...No DIG 31900 OM002 78...
Page 80: ...No DIG 31900 OM002 79...
Page 81: ...No DIG 31900 OM002 80...
Page 82: ...No DIG 31900 OM002 81...
Page 83: ...No DIG 31900 OM002 82...
Page 84: ...No DIG 31900 OM002 83...