No.DIG-31900-OM002
18
■
Barrier
A user should select a barrier suitable to each function. For an input circuit, use a barrier that is
linear resistance type based on intrinsically safe parameters. SMC verifies operation of IP8101
type smart positioner with the barrier shown on Table 8.
Table 8
Manufacturer
Model
Remark
For input current
(for non-HART communication)
FUCHS Inc.
KFD2-CD-Ex1.32
-
For input current
(for HART communication)
FUCHS Inc.
KFD2-SCD-Ex1.LK
-
For analog output
FUCHS Inc.
KFD2-STC4-Ex1
-
For alarm output
FUCHS Inc.
KFD2-SOT2-Ex2
Transistor output
passive type
FUCHS Inc.
KFD2-ST2-Ex2
Transistor output
active type
FUCHS Inc.
KFD2-SR2-Ex2.W
Relay output
Fig. 13
Barrier
Hazardous area
Non-hazardous area
Positioner
Actuator
Input current
Option output power supply
Controller
Fig. 12
Grounding
Input current
Analog output
Alarm output
Cable gland
M20×1.5
(uses twisted wire of 2.63
~
6.64mm
2
)
Terminal lug
M4 screw for internal
grounding terminal connection
G
Summary of Contents for IP8101 Series
Page 1: ...No DIG 31900 OM002 H SMART POSITIONER ROTARY TYPE PRODUCT NAME IP8101 Series MODEL Series...
Page 15: ...No DIG 31900 OM002 14 Table 6 Piping Layout...
Page 75: ...No DIG 31900 OM002 74 Drawing...
Page 76: ...No DIG 31900 OM002 75...
Page 77: ...No DIG 31900 OM002 76...
Page 78: ...No DIG 31900 OM002 77...
Page 79: ...No DIG 31900 OM002 78...
Page 80: ...No DIG 31900 OM002 79...
Page 81: ...No DIG 31900 OM002 80...
Page 82: ...No DIG 31900 OM002 81...
Page 83: ...No DIG 31900 OM002 82...
Page 84: ...No DIG 31900 OM002 83...