IDX-OM-M051
Air Dryer
3.Start and stop
3.3 Stop
3 - 2
IDF100F~150F-W
6) - The refrigerator is operated continuously, and the evaporation thermometer indicates the green
area.
If the evaporation thermometer exceeds the green area (indicates a higher temperature), refer
to “Chapter 5 Troubleshooting”.
7) A while after the compressed air starts being supplied, the drain tube will drain condensate
automatically.
8) Keep operation in that condition.
Caution
- Frequently turning on and off the switch can cause failure.
- Since the auto drain of the product is designed in such a way that the valve closes at
0.05MPa or higher (N.C. type), air will blow out from the drain port when the pressure
increases. Therefore, if the air compressor has a small air delivery, the pressure may not
be sufficient.
3.3 Stop
1) Turn off the switch with lamp.
For remote operation, turn off the external switch as well.
2) The lamp will go off and operation will stop.
3.4 Precautions for restarting operation
- Allow at least 3 minutes before restarting the product. If the product is restarted within 3 minutes after
being stopped, the protection circuit will be activated, operating light will turn off and the dryer will not be
activated.
If operation cannot be restarted, refer to “Chapter 5 Troubleshooting” to solve it.
3.5 Check items after starting
Check the following items when starting the product. Immediately stop the operation in the event of failure.
Turn off the switch with lamp and shut off the breaker of the main power supply.
- There is no leakage of compressed air and facility water.
- The pressure, temperature, flow rate and ambient temperature of the compressed air are within the
specified range.
- The pressure and temperature of the facility water are within the specified range.
- Condensate is coming out from the drain tube.
- The evaporation temperature meter is in the green area.
- There is no abnormal sound, vibration or odor from the product.