5. Troubleshooting
5.3 Reset of ground fault circuit interrupter (Option R)
5 - 4
IDF100F~150F-W
5.3 Reset of ground fault circuit interrupter (Option R)
When the ground fault circuit interrupter is triggered, all lamps will go off.
Eliminate the cause that triggered the ground fault circuit interrupter (ground fault, over current, etc.).
The ground fault display button (white) has popped up
Æ
Ground fault
The ground fault display button (white) remains pressed
Æ
Over current
1. Turn off the switch with lamp of the product.
2. Remove the front panel.
3. Bring the lever of the ground fault circuit interrupter down to the OFF position.
4. Lift up the lever from the OFF position to the ON position.
5. Put back the front panel.
6. Turn on the switch with lamp to restart operation.
Ground fault display button (white)