IDX-OM-M051
Air Dryer
6. Reference
6 - 1
IDF100F~150F-W
6.1 Specification table
Model
Item
IDF100F-30
-
□
W
□
IDF125F-30
-
□
W
□
IDF150F-30
-
□
W
□
O
pe
rati
ng
r
a
ng
e
Fluid
Compressed air
Inlet air temperature
o
C
5 to 60
Inlet air pressure MPa
0.25 to 1.0 / 0.15 to 1.6 for option K
Ambient temperature (humidity)
o
C
2 to 45 (Relative humidity 85% or less)
Facility water pressure MPa
0 . 2 to 0 . 9 8
Facility water inlet temperature
o
C
5 to 4 0
Rate
d
Note 3)
Air flow
capacity
m
3
/min
Standard
conditions
(ANR)
Note 1)
50Hz
16
2 0 . 1
2 5
60Hz
18.8
2 3 . 7
3 0
Air compressor suction
condition
Note 2)
50Hz
16.7
2 0 . 9
2 6
60Hz
19.6
2 4 . 7
3 1 . 2
Inlet air pressure MPa
0 . 7
Inlet air temperature
o
C
4 0
Ambient temperature
o
C
3 2
Outlet dew point
o
C
1 0
Amount of facility water (50/60Hz)
Note 5)
m
3
/ h
1 . 2 9 / 1 . 5 6
1 . 7 4 / 1 . 9 8
2 . 1 6 / 2 . 5 3
Facility water inlet temperature
o
C
3 2
Facility water pressure drop (50/60Hz)
Note 6)
MPa
0 . 0 7 to 0 . 1
Cooling tower capacity
Note 7)
kW (RT )
9 ( 2 )
11 . 5 ( 2 . 5 )
1 4 . 5 ( 3 . 2 )
E
le
ct
ric
sp
e
ci
fic
a
tio
n
s
Power supply voltage (frequency)
3 phase AC200V (50Hz) / AC200,220V (60Hz)
Power consumption (50/60Hz) kW
2 . 4 / 2 . 8
2 . 8 / 3 . 3
Operating current (50/60Hz) A
8 . 5 / 9 . 0
1 0 . 2 / 11 . 5
Applicable ground fault circuit interrupter capacity
Note 4)
A
2 0
3 0
Refrigerant
R407C (HFC)
Auto drain
Float type (N.O)
Timer controlled auto drain for option V
Port size
R 2
J I S F l a n g e
6 5 A 1 0 K
J I S F l a n g e
8 0 A 1 0 K
( F o r O p t i o n K
:
1 6 K )
Weight kg
2 2 6
2 5 0
3 2 2
Coating color
Panel: Urban white 1 / Base: Urban gray 2
Applicable air compressor (screw type) output (referential) kW
1 0 0
1 2 5
1 5 0
Note 1) Air flow capacity under the standard condition (ANR) [20
o
C atmospheric pressure and 65% relative humidity].
Note 2) Air flow capacity calculated for atmospheric condition [32
o
C, atmospheric pressure]
Note 3) For specifications other than the rated specifications, select the model referring to the selection method.
Reference
6
6.1
Specification table