-78-
No.EX##-OMN0030-A
•Channel parameter object (2) (Class: 83h to 8Ah) [
DeviceNet
TM
extended object library 2]
Class Instance Attribute
Access
Name
Type
Value
83h
Output setting at the
time of communication
error
•SI
•Digital O, I/O
•Analog O, I/O
BOOL
0=Disable (Hold)
1=Enable (Clear or Force ON)
84h
Output setting at the
time of communication
error (Digital)
•SI
•Digital O, I/O
BOOL
0=OFF (Clear)
1=ON (Force ON)
85h
Output setting at the
time of communication
error (Analog)
•Analog O, I/O
UINT
86h
Output setting at the
time of communication
idling
•SI
•Digital O, I/O
•Analog O, I/O
BOOL
0=Disable (Hold)
1=Enable (Clear or Force ON)
87h
Output setting value at
the time of
communication idling
(Digital)
•SI
•Digital O, I/O
BOOL
0=OFF (Clear)
1=ON (Force ON)
88h
Output setting value at
the time of
communication idling
(Analog)
•Analog O, I/O
UINT
89h
Analog average filter
•Analog I, I/O
USINT
0=None
1=2 value average
2=4 value average
3=8 value average
8Ah
01h to
0Ah
∗
1
64h to
83h
∗
2
Get/Set
Analog range
•Analog I, O, I/O
USINT
0=-10…+10 V
(Analog input unit only)
1=-5…+5 V
(Analog input unit only)
2=-20…+20 mA
(Analog input unit only)
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20mA
7=4…20mA
∗
1: 01h to 0Ah indicates the unit number 0 to 9.
∗
2: 64h to 83h indicates the channel number 0 to 31.