![SMC Networks EX600-ED Series Operation Manual Download Page 72](http://html1.mh-extra.com/html/smc-networks/ex600-ed-series/ex600-ed-series_operation-manual_1299354072.webp)
-71-
No.EX##-OMN0030-A
•Analog Input Unit object (Class:6Dh) [
DeviceNet
TM
extended object library 1]
Instance
Attribute
Access
Name
Type
Value
70h Get/Set
Monitor short circuit at Power
Supply
BOOL
0=Disable
1=Enable
74h
Get/Set Monitor over range
BOOL
0=Disable
1=Enable
75h
Get/Set Monitor under range
BOOL
0=Disable
1=Enable
A4h
Get/Set Ch0 analog input filter
USINT
0=None
1=2 value average
2=4 value average
3=8 value average
A5h
Get/Set Ch1 analog input filter
USINT
0=None
1=2 value average
2=4 value average
3=8 value average
A8h
Get/Set Ch0 analog range
USINT
0=-10…+10 V
1=-5…+5 V
2=-20…+20 mA
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
A9h
Get/Set Ch1 analog range
USINT
0=-10…+10 V
1=-5…+5 V
2=-20…+20 mA
3=0…10 V
4=0…5 V
5=1…5 V
6=0…20 mA
7=4…20 mA
01h to 10h
ACh
Get/Set Analog data format
USINT
0=Offset Binary
1=Sign & Magnitude
2=2’s complement
Summary of Contents for EX600-ED Series
Page 29: ...28 No EX OMN0030 A Dimensions...
Page 33: ...32 No EX OMN0030 A EX600 ED3...