-13-
No.EX##-OMN0030-A
•Assembling the unit as a manifold
∗
: If the unit was purchased as a manifold, the work described in this section is not necessary.
(1)Connect a unit to the end plate.
Digital and Analog I/O units can be connected in any order.
Tighten the joint brackets to a torque of 1.5 to 1.6 Nm.
(2)Add more I/O units.
Up to 10 units (including the SI unit) can be connected to one manifold.
(3)Connecting the SI unit.
After connecting the required I/O units, connect the SI unit.
The method is as above in (1), (2).