-50-
No.EX##-OMN0030-A
•Analog input unit parameters
Parameter
setting
No.
Parameter
(H.T. Symbol)
Definition
Item
Content
Default
setting
By
EDS
By
H.T.
Enable Generates
an
error.
○
1
The power
supply short
circuit
detection for
the input
device
(SC_MonSs)
Generates error
per unit when the
short circuit of the
power supply for
the input device is
detected.
Disable
Does not generate an
error.
○
○
-10..10 V
-5..5 V
-20..20 mA
0..10 V
0..5 V
1..5 V
0..20 mA
2
Analog input
range
(Range)
Set the analog
input device range
per channel.
4..20 mA
Selects the analog
input range.
-10..10 V
○
○
Offset binary
Offset binary.
○
Sign & Magnitude
Signed binary.
3
Analog data
format
(D_Format)
Sets analog data
type which is output
to PLC per unit.
2s complement
2’s complement.
○
○
None None.
2AVG
2 value average.
○
4AVG
4 value average.
4
Analog
average filter
(Filter)
Sets analog
filtering time per
channel.
Sampling interval is
approx. 2 sec.
8AVG
8 value average.
○
○
Enable Generates
an
error.
○
5
Over range
detection
(Over_Rng)
Generates error
per unit when the
input value
exceeds 0.5% of
full span.
Disable
Does not generate an
error.
○
○
Enable Generates
an
error.
○
6
Under range
detection
(Undr_Rng)
Generates error
per unit when the
input value falls
below 0.5% of full
span.
Disable
Does not generate an
error.
○
○
Enable Generates
an
error.
∗
1
7
User setting
value upper
limit error
(Upr_Lmt)
Generates error
per unit when the
input value
exceeds the set
value.
Disable
Does not generate an
error.
○
∆
∗
2
○
Enable Generates
an
error.
∗
1
8
User setting
value lower
limit error
(Lwr_Lmt)
Generates error per
channel when the
input value falls
below the set value. Disable
Does not generate an
error.
○
∆
∗
2
○
∗
1: Set value shall be set per analog input range within settable range in the table below.
When the analog input range is changed,
check the set value and change it to an appropriate value.
∗
2: It is possible to set it only with DeviceNet
TM
extended object library 2.