•Unit/Channel diagnosis object (Class: 67h) [

DeviceNet

TM

 extended object library 2]

 

Instance  Attribute  Access 

Name 

Type 

Value 

6Ch 

Get 

Unit diagnosis 

BYTE

Bit0: Analog user set value lower limit detection 
Bit1: Analog user set value upper limit detection 
Bit2: Analog range lower limit detection 
Bit3: Analog range upper limit detection 
Bit4: Contact frequency upper limit detection 
Bit5: Open circuit detection 
Bit6: Short circuit detection (Output) 
Bit7: Short circuit detection   

(Power supply for input/output device) 

6Eh 

Get 

Channel diagnosis 

Ch0 to Ch7 

BYTE

Bit0: Error is detected in channel 0 

Bit7: Error is detected in channel 7 

6Fh 

Get 

Channel diagnosis 

Ch8 to Ch15 

BYTE

Bit0: Error is detected in channel 8 

Bit7: Error is detected in channel 15 

70h 

Get 

Channel diagnosis 

Ch16 to Ch23 

BYTE

Bit0: Error is detected in channel 16 

Bit7: Error is detected in channel 23 

01h to 

0Ah 

1

 

71h 

Get 

Channel diagnosis 

Ch24 to Ch31 

BYTE

Bit0: Error is detected in channel 24 

Bit7: Error is detected in channel 31 

1: 01h to 0Ah indicates the unit number 0 to 9. 

 

 

•Details of channel diagnosis object (Class: 77h) [

DeviceNet

TM

 extended object library 2]

 

Instance  Attribute 

Access 

Name 

Type 

Value 

01h to 

0Ah 

64h to 

83h 

Get 

Channel diagnosis 

Ch0 to 31 

BYTE

Bit0: Analog user set value lower limit detection 
Bit1: Analog user set value upper limit detection 
Bit2: Analog range lower limit detection 
Bit3: Analog range upper limit detection 
Bit4: Contact frequency upper limit detection 
Bit5: Open circuit detection 
Bit6: Short circuit detection (Output) 
Bit7: Short circuit detection 

(Power supply for input/output device) 

1: 01h to 0Ah indicates the unit number 0 to 9. 

2: 64h to 83h indicates the channel number 0 to 31. 

Summary of Contents for EX600-ED Series

Page 1: ...No EX OMN0030 A Fieldbus system DeviceNetTM compatible SI unit PRODUCT NAME EX600 SDN A EX600 ED MODEL Series...

Page 2: ...I Unit Model Indication and How to Order 18 Names and Functions of Product 18 Mounting and Installation 19 Wiring 19 Setting and Adjustment 20 LED Display 25 Specification 27 Specifications 27 Dimensi...

Page 3: ...ing 34 Parameter Setting 43 Parameter definition and setting 43 Hardware Configuration 56 ESD file and icon 56 Setting using RSNetWorx for DeviceNetTM 57 I O Map 61 Diagnostic 62 Details of diagnostic...

Page 4: ...continuously review all specifications of the product referring to its latest catalog information with a view to giving due consideration to any possibility of equipment failure when configuring the...

Page 5: ...arts Please consult your nearest sales branch 2 For any failure or damage reported within the warranty period which is clearly our responsibility a replacement product or necessary parts will be provi...

Page 6: ...he product outside of the specifications Do not use for flammable or harmful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmos...

Page 7: ...duct The instructions on design and selection installation wiring environment adjustment operation maintenance etc described below must also be followed Product specifications The direct current power...

Page 8: ...m proper insulation of wiring Poor insulation interference from another circuit poor insulation between terminals etc can lead to excess voltage or current being applied to the product causing damage...

Page 9: ...hes by using a sharp pointed screwdriver etc When setting the switch do not touch other unrelated parts This can cause parts damage or malfunction due to a short circuit Perform settings suitable for...

Page 10: ...ith switch output capability PNP and NPN types are available Digital output unit For connecting output device such as solenoid valves lamps buzzers etc PNP and NPN types are available Digital I O unit...

Page 11: ...th F Fieldbus The protocol that uses digital communication to exchange signals between field equipment instruments and actuators running on site and a PLC H Handheld Terminal H T Connected to the dedi...

Page 12: ...it detection A diagnosis function to detect an over current due to the short circuit of the output and or power supply positive line with respect to the GND line Short circuit protection A function to...

Page 13: ...A EX600 DX B EX600 DX C EX600 DX D EX600 DX E Digital input unit EX600 DX F EX600 DY B EX600 DY E Disital output unit EX600 DY F EX600 DM E Digital I O unit EX600 DM F Analog input unit EX600 AXA Anal...

Page 14: ...nnect a unit to the end plate Digital and Analog I O units can be connected in any order Tighten the joint brackets to a torque of 1 5 to 1 6 Nm 2 Add more I O units Up to 10 units including the SI un...

Page 15: ...QC1000 2 places VQC2000 3 places VQC4000 4 places SY 2 places 5 Connect the SI unit to the valve manifold Insert the valve plate into the valve plate mounting groove on the side of the SI unit Fix usi...

Page 16: ...reinforcing brace EX600 ZMB1 before mounting using 2 M4x5 screws Tightening torque 0 7 to 0 8 Nm Intermediate reinforcing brace EX600 ZMB1 2 Mount and tighten the end plate at one end of the unit M4...

Page 17: ...et EX600 ZMA2 to the end plate at the opposite end to the valves using 2 M4x14 screws Tightening torque 0 7 to 0 8 Nm 3 Hook the DIN rail mounting groove on to the DIN rail 4 Press the manifold using...

Page 18: ...ically If they are not aligned the connector cannot be connected correctly 3 When mark B has been turned 180 degrees 1 2 turn wiring is complete Confirm that the connection is not loose If turned too...

Page 19: ...w Screw to open the display cover 4 Connector BUS OUT Connecter for Fieldbus outputs 5 Marker groove Groove for an identification marker 6 Connector PCI Connecter for Handheld Terminal 7 Valve plate m...

Page 20: ...e SI unit use a DeviceNet tap rather than marking connections to the BUS OUT connector Circuit diagram The product has T branching internally in the unit as shown in the circuit diagram below It can b...

Page 21: ...ew in the reverse order of the above procedure Tightening torque 0 3 to 0 4 Nm Precautions for handling Turn off the power supply whilst setting the switch If there is foreign matter or water droplets...

Page 22: ...Sets the 1 digit of the DeviceNet node address Data Rate switch Sets DeviceNet communication speed Address setting Data Rate setting Address x10 x1 Node Address 0 0 0 Default setting 0 1 1 0 2 2 6 2 6...

Page 23: ...OFF ON Number of valves 24 outputs 3 byte ON OFF Number of valves 16 outputs 2 byte ON ON Number of valves 8 outputs 1 byte Set the number of occupied valve outputs to at least the number of valves u...

Page 24: ...2 Input data System diagnosis Unit diagnosis Up to 10 units 6 byte ON ON 3 Input data System diagnosis Unit diagnosis Up to 64 units 12 byte Mode 3 is a function for extension in the future Do not use...

Page 25: ...is switched ON the system will compare the stored configuration with the manifold configuration If the configuration is different diagnostic error will be generated Settings2 5 Content OFF Normal ope...

Page 26: ...LEDs are ON The unit is in normal operation Red ST M LED is ON A component failure inside the SI unit Red PWR LED is ON The power supply voltage for control and input is abnormal Red PWR V LED is ON T...

Page 27: ...that of the slave If they are not the same correct them Check proper length of the cable Check the communication cable is not disconnected or loose Ensure that the terminal resistor is mounted proper...

Page 28: ...with LED and circuit protection Power supply 24 VDC 2 A Output for communication error HOLD CLEAR Force ON Output specifications Protective function Short circuit protection Enclosure IP67 With manifo...

Page 29: ...28 No EX OMN0030 A Dimensions...

Page 30: ...racket Specified for SY series 3 7 8 inch 5 pin Names and Functions of Product EX600 ED2 EX600 ED3 No Description Function 1 Power connector Supplies power for each unit and input output device 2 Fixi...

Page 31: ...er supply This product has 2 power supplies and it is divided as follows Power supply for control and input Supplying power for control of each unit s power supply for control and also for device conn...

Page 32: ...dity range 35 to 85 RH No condensation Withstand voltage 500 VAC for 1 minute between external terminals and FE Insulation resistance 500 VDC 10 M min between external terminals and FE Vibration resis...

Page 33: ...32 No EX OMN0030 A EX600 ED3...

Page 34: ...ring Connect properly if the connection is loose Seal cap Tighten properly if the connection is loose Thread for mounting and installation If the thread is loose re tighten it to the specified torque...

Page 35: ...ldbus system breakage can be caused by the operating environment Contact SMC separately to obtain countermeasures Yes No Refer to failure 7 Refer to failure 6 Refer to failure 5 Refer to failure 3 Ref...

Page 36: ...ly The valve does not work correctly Red ST M LED is ON Or red green ST M LED is flashing alternately Red PWR or PWR V LED is ON Red MS or NS LED is ON Contact SMC SI unit Red ST M LED is flashing Ref...

Page 37: ...set value 2 The wire of the input device is broken or disconnected Only EX600 DX C1 Check the parts with error by using the LED display or PLC or H T 1 Reset the ON OFF count to zero or change the se...

Page 38: ...zero or change the set value Or invalidate diagnosis 2 Check if the connector is loose and if the wire is broken 3 DY E DY F Red green ST LED is flashing Unit has failed Stop the operation and contac...

Page 39: ...ce exceeds the upper or lower limit of the range select the appropriate range so that the input value is within the range Or invalidate diagnosis 2 If the input value from the analog input device exce...

Page 40: ...e user set value adjust it so that the input output value is within the range of the user set value Or invalidate diagnosis 7 AMB Red green all LEDs are flashing Unit has failed Stop the operation and...

Page 41: ...rces away from the communication line The number of connected valves is larger than the number of occupied valve outputs When the number of occupied valves of the V_SEL switch is smaller than the numb...

Page 42: ...normal one and check the operation Or refer to the troubleshooting of the input device used Polarity of output does not match If the polarity PNP NPN of the output unit and the output device are diff...

Page 43: ...one and check the operation Or refer to the troubleshooting of the analog input device used Power supply for output is abnormal Check if the green PWR V LED of the SI unit is ON If the LED is OFF or t...

Page 44: ...t all outputs 1 Hold Clear priority setting Hold Clear Switch the setting of the output during communication error or communication idling to follow the SI unit switch or the parameters Handheld Setti...

Page 45: ...able Does not generate an error Auto Error is automatically cleared when the short circuit is fixed 4 Restart after short circuit SC_RstOp Restore the setting of short circuit detection error per unit...

Page 46: ...operation count exceeds the set value 3 Disable Does not generate an error 5 1 This function is valid only when Hold Clear priority of the system parameter is set to H T 2 Some PLC does not support an...

Page 47: ...e SigExt_T Sets the time to hold the input signal per unit 200 ms Selects the time to hold the input signal 15 ms Enable Generates an error Val 1 to 65000 4 6 Channel ON OFF counter Counter Memorizes...

Page 48: ...t setting during communication fault 2 Fault_MD Set output per channel when communication is abnormal ForceON Turn on the output forcefully 6 Clear Turn off the output Hold Hold the output 5 Output se...

Page 49: ...ror 5 Output load short circuit detection SC_MonOp Generates error per unit when the short circuit of the output device is detected 1 Disable Does not generate an error Auto Error is automatically cle...

Page 50: ...Does not generate an error 6 1 Could be incorrectly recognized as short circuit depending on used load ex lamp load If detection is incorrect disable the parameter setting 2 This function is valid onl...

Page 51: ...per channel Sampling interval is approx 2 sec 8AVG 8 value average Enable Generates an error 5 Over range detection Over_Rng Generates error per unit when the input value exceeds 0 5 of full span Dis...

Page 52: ...10 10 V 10 50 to 10 45 V 10 45 to 10 50 V 5 5 V 5 25 to 5 22 V 5 22 to 5 25 V 20 20 mA 21 00 to 20 90 mA 20 90 to 21 00 mA 0 10 V 0 00 to 10 45 V 0 05 to 10 50 V 0 5 V 0 00 to 5 22 V 0 03 to 5 25 V 1...

Page 53: ...pr_Lmt Generates error per channel when the output value exceeds the set value Disable Does not generate an error Enable Generates an error Val 32766 to 32767 4 Scale upper limit setting 1 UpLm Scl Se...

Page 54: ...When the analog input range is changed check the set value and change it to an appropriate value 3 This function is valid only when Hold Clear priority of the system parameter is set to Handheld 4 Som...

Page 55: ...ion type None None 2AVG 2 value average 4AVG 4 value average 4 Analog average filter Filter Sets analog filtering time per channel Sampling interval is approx 2 sec 8AVG 8 value average Enable Generat...

Page 56: ...Sets output per channel during communication idling Disable Output will be held last state 5 1 When Scaled is selected as the analog data format the display of H T is switched from Upr_Lmt to UpLm Sc...

Page 57: ...0_sdn2_v16 zip EDS file ex600_sdn2_v16 eds Icon ex600_1 ico Content of ex600_sdn1_v22 zip EDS file ex600_sdn1_v22 eds Icon ex600_1 ico Content of ex600_sdn2_v22 zip EDS file ex600_sdn2_v22 eds Icon ex...

Page 58: ...f operation The screen data shown here is the English version of RSNetWorx for DeviceNet TM verion 5 00 00 EDS file install 1 Start RSNetWorx for DeviceNetTM 2 Select EDS Wizard from Tools 3 The EDS f...

Page 59: ...ick EX600 SDN on the Hardware screen 2 The icon of EX600 SDN is displayed on the Network screen Address setting of EX600 1 Double click EX600 SDN on the Network screen 2 EX600 SDN property screen is d...

Page 60: ...A Setting of the scan list 1 Double click the scanner icon on the Network screen 2 1756 DNB A property screen is displayed Click the Scanlist tab 3 Select EX600 SDN in Available Devices and click on...

Page 61: ...eters 1 Double click the EX600 SDN on the Scanlist 2 Edit I O parameters screen is displayed Input I O Parameters and click on OK Please leave unticked the Strobed and Change of State Cyclic tick boxe...

Page 62: ...ction 1 0 EX600 DX D 16 inputs 2 0 EX600 DX E 16 inputs 2 0 Digital input unit EX600 DX F 16 inputs 2 0 EX600 DY B 8 outputs 0 1 EX600 DY E 16 outputs 0 2 EX600 DY E1 24 outputs 0 3 Digital output uni...

Page 63: ...ustment for setting the switch Mode Diagnostic Data Diagnostic Size 0 No diagnostic data 0 byte 1 System diagnosis 4 byte 2 System diagnosis Unit diagnosis Up to 10 units 6 byte 3 System diagnosis Uni...

Page 64: ...gital input 2 byte Input SDN A SI unit 32 output 4 byte Output Valve Input data Analog input unit EX600 AXA _4 byte occupied Unit 0 Digital input unit EX600 DX B _1 byte occupied Unit 3 Digital input...

Page 65: ...channel 1 Unit 0 Byte8 DX B Unit 3 Byte9 Byte10 DX D Unit 4 Total 11 byte 6 byte Diagnostic mode 2 Input data Output data Byte0 System diagnosis byte0 DY B Unit 1 Byte1 System diagnosis byte1 DY B Un...

Page 66: ...ification 1 The power supply voltage for control and input device is outside of the specification 2 Reserved 3 There is a connection failure between each unit During operation 4 There is a connection...

Page 67: ...re is an error in unit 2 3 There is an error in unit 3 4 There is an error in unit 4 5 There is an error in unit 5 6 There is an error in unit 6 7 There is an error in unit 7 Unit diagnosis byte1 Bit...

Page 68: ...1h Unit channel diagnosis 67h 01h to 0Ah 2 Details of channel diagnosis 77h 01h to 0Ah 2 Unit parameter 78h 01h to 0Ah 2 Channel parameter 1 79h to 7Fh 01h to 0Ah 2 DeviceNet TM extended object librar...

Page 69: ...5 Configuration memory error Bit6 System error Bit7 Hardware error Bit8 Analog user set value lower limit detection Bit9 Analog user set value upper limit detection Bit10 Analog range lower limit dete...

Page 70: ...1 Reserved Bit12 Reserved Bit13 Reserved Bit14 Reserved Bit15 Reserved 95h Get Unit Diagnostics 2 WORD Reserved 96h Get Unit Diagnostics 3 WORD Reserved 97h Get Unit Diagnostics 4 WORD Reserved 98h Ge...

Page 71: ...utput Unit object Class 6Bh DeviceNet TM extended object library 1 Instance Attribute Access Name Type Value 71h Get Set Monitoring short circuit at Output BOOL 0 Disable 1 Enable 01h to 40h 7Bh Get S...

Page 72: ...A4h Get Set Ch0 analog input filter USINT 0 None 1 2 value average 2 4 value average 3 8 value average A5h Get Set Ch1 analog input filter USINT 0 None 1 2 value average 2 4 value average 3 8 value av...

Page 73: ...average 2 4 value average 3 8 value average A5h Get Set I Ch1 analog input filter USINT 0 None 1 2 value average 2 4 value average 3 8 value average A8h Get Set I Ch0 analog range USINT 3 0 10 V 4 0...

Page 74: ...Get Set Input filtering time USINT 0 0 1 ms 1 1 0 ms 2 10 ms 3 20 ms 01h to 40h A8h Get Set Input extension time USINT 0 1 0 ms 1 15 ms 2 100 ms 3 200 ms Analog Output Unit object Class 71 h DeviceNe...

Page 75: ...t device 7Bh Get System diagnosis 2 BYTE Bit0 Monitoring the power supply voltage For output Bit1 Monitoring the power supply voltage For control and input Bit2 Reserved Bit3 Number of units not conne...

Page 76: ...annel 15 70h Get Channel diagnosis Ch16 to Ch23 BYTE Bit0 Error is detected in channel 16 Bit7 Error is detected in channel 23 01h to 0Ah 1 71h Get Channel diagnosis Ch24 to Ch31 BYTE Bit0 Error is de...

Page 77: ...e against in rush current Digital I I O BOOL 0 Disable 1 Enable 69h Get Set Recovery after a short circuit SI Digital O I O BOOL 0 Manual 1 Auto 6Ah Get Set Input filtering time Digital I I O USINT 0...

Page 78: ...unt upper limit value SI Digital I O I O UINT 1 to 65000 Times diagnosis is detected Set value x1000 7Ch Analog user set value upper limit detection Analog I O I O BOOL 0 Disable 1 Enable 7Dh Analog u...

Page 79: ...unication idling SI Digital O I O Analog O I O BOOL 0 Disable Hold 1 Enable Clear or Force ON 87h Output setting value at the time of communication idling Digital SI Digital O I O BOOL 0 OFF Clear 1 O...

Page 80: ...screw M4x6 2 pcs Round head screw M3x8 2 pcs 2 End plate bracket EX600 ZMA2 Enclosed parts Round head screw M4x20 1 pc P tight screw 4x14 2 pcs EX600 ZMA3 Specified for SY series Enclosed parts Round...

Page 81: ...aight 2 m PCA 1558823 Cable with 7 8 inch connector Socket Straight 6 m PCA 1558836 Cable with 7 8 inch connector Socket Right angle 2 m PCA 1558849 Cable with 7 8 inch connector Socket Right angle 6...

Page 82: ...N0030 A Revision history A Modify an error in writing Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2010 SMC Corporation All Rights...

Reviews: