-18-
No.EX##-OMM0008-B
Discrete Output Point (DOP) object (0x09)
ID
Meaning
GET
SET
Value
0x01 Revision
О
-
0001H
Attributes
0x02 Max Instance
О
-
Number of output
points
Cord
Meaning
Parameter option
Object class
Services
0x0E Get_Attribute_Single -
ID
Meaning
GET
SET
Value
0x05 Fault Action
О
О
Sets the output
condition for
communication error.
0: Zero clear
1: Hold output
The set value is
immediately reflected.
0x07 Idle Action
О
О
Setting of the output
when the control is
abnormal.
0: Zero clear
1: Hold output
The set value is
immediately reflected.
0x65
Maintenance Counter
Mode Choice
О
О
Setting of mode of
maintenance counter
0: Energizing time
mode (hour)
1: Contact counter
mode (time)
The set value is
immediately reflected.
0x66 Maintenance Counter
О
О
Present value of
maintenance counter
0 to 4294967295
(00000000 to
FFFFFFFF H)
0x67
Maintenance Counter
Exceed
О
-
Maintenance counter
threshold over flag
0: Maintenance counter
value < Threshold
1: Maintenance counter
value > Threshold
Attributes
0x68
Threshold Maintenance
Counter
О
О
Threshold of
maintenance counter
0 to 4294967295
(00000000 to
FFFFFFFF H)
The set value is
immediately reflected.
Cord
Meaning
Parameter option
0x05 Reset Only
Attribute66
0x0E Get_Attribute_Single -
Object instance
Services
0x10 Set_Attribute_Single -