-11-
No.EX##-OMM0008-B
1, Communication wiring
The network cable and communication connector for CompoNet
TM
are connected in the following
manner.
Note
The communication connector for the SI unit should be as shown below.
Communication connector
SMC
OMRON
HONDA TSUSHIN
KOGYO
For flat ribbon cable: IDC connector
EX9-CCM1
DCN4-BR4
-
For round cable: Terminal block connector
EX9-CCM2
-
HCN-
We do not provide a tool that is used for wiring IDC connector.
Please contact OMRON for further details.
•
Connection of IDC connector for flat ribbon cable
1, Cutting of cable
Cut the cable vertically.
Use a tool with sharp edges such as a nipper to prevent short-circuit, and check there are no
whiskers of wire sticking out.
2, Connection of cable
Match the cable identification color with the color of the cable and insert the cable.
The cover is translucent to make it possible to check the cable reaches the end.
3, Pressure-welding the connector
Use a tool (OMRON, DWT-A01) to connect wires.
(1) As shown below, place the connector cover so that its center (arrowed part) is at the center of
the IDC block of the tool.