HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 41 of 58
29
Close Generator
Control generator to take load.
30
Open Breaker
Control generator to off load.
31
Close Mains
Control mains to take load.
32
Reserved
33
Start Relay
34
Fuel Relay
Action
when
genset
is
cranking
and
disconnect when stopped completely.
35
Idle Control
Used for engine which has idles. Close before
starting and open in warming up delay; Close
during stopping idle mode and open when
stop is completed.
36
Raise Speed
Action in warming up delay.
37
Drop Speed
Action between the period from
“stop idle” to
“failed to stop”.
38
ETS Control
Used for engines with ETS electromagnet.
Close when stop idle is over and open when
pre-
set “ETS delay” is over.
39
Reserved
40
Reserved
41
Reserved
42
Reserved
43
Crank Success
Close when detects a successful start signal.
44
Generator OK
Action when generator is normal.
45
Generator Available
Action in period of generator ok to hi-speed
cooling.
46
Mains OK
Action when mains normal.
47
Reserved
48
Common Alarm
Action when genset common warning,
common shutdown, common trips alarm.
49
Common Trip and Stop
Action when common trip and stop alarm.
50
Common Shutdown
Action when common shutdown alarm.
51
Common Trip Alarm
Action when common trips alarm.
52
Common Warn Alarm
Action in common warning alarm.
53
Reserved
54
Battery High Volts
Action when
battery‟s over voltage warning
alarm.
55
Battery Low Volts
Action when
battery‟s low voltage warning
alarm.
56
Charge Alt Fail
Action when charge failure warning alarms.
57
Reserved
58
Reserved
59
Reserved
60
Reserved
61
Reserved
62
Reserved