![Smartgen HGM9120 User Manual Download Page 29](http://html1.mh-extra.com/html/smartgen/hgm9120/hgm9120_user-manual_1297531029.webp)
HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 29 of 58
No.
Function
Cable
Size
Remarks
10
High Temp.
1.0mm
2
Ground
connected
is
active (B-)
Details see form
3
11
Low Oil Temperature
1.0mm
2
Ground
connected
is
active (B-)
12
Low Fuel Level
1.0mm
2
Ground
connected
is
active (B-)
13
Remote Start
1.0mm
2
Ground
connected
is
active (B-)
14
Aux. Input 1
1.0mm
2
Ground
connected
is
active (B-)
15
Aux. Input 2
1.0mm
2
Ground
connected
is
active (B-)
16
Magnetic Pickup
0.5mm
2
Connected with Speed sensor, shielding line is
recommended. (B-) has already connected
with speed sensor 2
17
Magnetic Pickup 2
18
Magnetic Pickup 1
19
Aux. Input 3
1.0mm
2
Ground
connected
is
active (B-)
Details see form
3
20
Aux. Output 2
1.0mm
2
Normally
close
output,
rated 7A
Details see form
2
21
Public points of relay
22
Normally
open
output,
rated 7A
23
Mains Close Input
1.0mm
2
Normally
close
output,
rated 7A
Details see form
2
24
1.0mm
2
Normally
open
output,
rated 7A
25
1.0mm
2
Public points of relay
26
Gen Close Input
1.0mm
2
Normally
open
output,
rated 7A
27
1.0mm
2
Public points of relay
28
Mains
A-phase
voltage sensing input
1.0mm
2
Connected to A-phase of mains (2A fuse is
recommended)
29
Mains
B-phase
voltage sensing input
1.0mm
2
Connected to B-phase of mains (2A fuse is
recommended)
30
Mains
C-phase
voltage sensing input
1.0mm
2
Connected to C-phase of mains (2A fuse is
recommended)
31
Mains N-wire input
1.0mm
2
Connected to N-wire of mains
32
Genset
A-phase
voltage sensing input
1.0mm
2
Connected to A-phase of gen-set (2A fuse is
recommended)
33
Genset
B-phase
voltage sensing input
1.0mm
2
Connected to B-phase of gen-set (2A fuse is
recommended)
34
Genset
C-phase
voltage sensing input
1.0mm
2
Connected to C-phase of gen-set (2A fuse is
recommended)