HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 36 of 58
No.
Items
Parameters
Defaults
Description
be added.)
Scheduling And Maintenance Setting
1
Scheduled
Run
(0~1)
0
0: Disable; 1: Enable
2
Scheduled
Not Run
(0~1)
0
0: Disable; 1: Enable
3
Maintenance (0~1)
0
0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1
Curve Types
(0~15)
7
SGX. See form 4.
2
Open Circuit
Action
(0~2)
0
0: Warn; 1: Shutdown; 2: No action
3
High
Temp.
Shutdown
(0~300)ºC
98
Shutdown when sensor temperature
higher than this value. Detecting only
after safety delay is over. The delay
value can be set.
4
High
Temp.
Warn
(0~300)ºC
95
Warn when sensor temperature higher
than this value. Detecting only after
safety delay is over. The delay value
and return value can be set.
5
Low
Temp.
Warn
(0~1)
0
0: Disable; 1: Enable
Oil Pressure Sensor
1
Curve Types
(0~15)
7
SGX. See form 4.
2
Open Circuit
Action
(0~2)
0
0: Warn 1: Shutdown 2: No action
3
Low
OP
Shutdown
(0~1000)kPa
103
Shutdown when oil pressure lower
than this value. Detecting only after
safety delay is over. The delay value
can be set.
4
Low OP Warn (0~1000)kPa
124
Warn when oil pressure lower than this
value. Detecting only after safety delay
is over. The delay value and return
value can be set.
Liquid Level Sensor
1
Curve Types
(0~15)
4
SGH. See form 4
2
Open Circuit
Action
(0~2)
0
0:Warn; 1:Shutdown; 2:No action
3
Low
Level
Warn
(0~300)%
10
Warn when level lower than this value.
It is detecting all the time. The delay
value and return value can be set.
Oil Temperature Sensor