HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 35 of 58
No.
Items
Parameters
Defaults
Description
value can be set as definite time and
inverse definite minimum time.
5
Over Power
(0~1)
0
0: Disable 1: Enable.
6
Reverse
Power
(0~1)
0
0: Disable 1: Enable.
7
Earth Current
Trans.
(5~6000)/5
500
The ratio of external earth CT.
8
Rated
Earth
Current
(5~6000)A
500
Generator‟s rated earth current
9
Earth Current
Setting
(0-200)%
20
Setting
value
is
percentage
of
generator rated earth current.
Switch Setting
1
Transfer Time (0~7200)s
5
Interval time from mains switch off to
generator switch on; or from generator
switch off to mains switch on.
2
Close Time
(0~20.0)s
5.0
Pulse width of mains/generator switch
on. When it is 0, means output
constantly.
3
Open Time
(0~20.0)s
3.0
Pulse width of mains/generator switch
off.
4
Check Time
(0~20.0)s
5.0
Time of detecting switch auxiliary
contacts after transferred.
5
Warn Enable
(0~1)
0
0: Disable 1: Enable.
6
Check Enable (0~1)
0
0: Disable 1: Enable.
7
Enable
Immediate
Mains
Dropout
(0~1)
1
0: Disable 1: Enable.
Module Setting
1
Power
on
Mode
(0~2)
0
0: Stop mode 1: Manual mode
2: Auto mode
2
Module
Address
(1~254)
1
Controller‟s address during remote
sensing.
3
Stop Bits
(0~1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0~2)
1
0: Reserved 1: English 2: Others
5
Password
(0~65535)
00318
It is used for entering advanced
parameters setting.
GSM Setting
1
GSM/RS232
(0~2)
2
0: Both Disable; 1: GSM Enable; 2:
RS232 Enable
2
Phone
Number
Max. 20 digits
Its national and area‟s cods must be
added. e.g. China: 8613666666666
(Care should be taken
“00” or “+” not