![Smartgen HGM9120 User Manual Download Page 15](http://html1.mh-extra.com/html/smartgen/hgm9120/hgm9120_user-manual_1297531015.webp)
HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 15 of 58
Note:
1. Input active power, generator or mains supply electricity to load.
2. Output active power, load supply electricity to generator or mains.
3. Input reactive power, generator or mains send reactive power to load.
4. Output reactive power, load send reactive power to generator or mains.
★
Alarm:
◙
Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or stop)
and the real time when alarm occurs.
Others
, including,
Time and Date, count down time for maintenance, input/output ports status.
◙
About,
including,
Issue time of software and hardware version
Example:
Engine-Speed
1500
r/min
Manual Mode
Power
Factor
Conditions
Active
Power
Inactive
Power
Remark
COS>0L
P>0,Q>0
Input
Input
Load is inductive resistance.
COS>0C
P>0,Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0,Q>0
Output
Input
Load equal to one under excitation
generator
COS<0C
P<0,Q<0
Output
Output
Load equal to one over excitation
generator.
Gen-Phase Voltage
L1 220V
L2 220V
L3 220V
Battery Undervolts