HGM9120 Genset Controller
HGM9120 Genset Controller Version: 1.0 2014-04-14 Page 38 of 58
No.
Items
Parameters
Defaults
Description
5
Description
LCD display detailed contents when
the input is active.
Low Oil Pressure Input
1
Active Type
(0~1)
0
0: Closed to active 1: Open to active
2
Arming
(0~3)
0
0: From safety on 1: From starting
2: Always 3:Never
3
Active Actions (0~4)
0
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
4
Active Delay (0~20.0)s
2.0
Time from detecting active to confirm
5
Description
LCD display detailed contents when
the input is active.
Low Fuel Level
1
Active Type
(0~1)
0
0: Closed to active 1: Open to active
2
Arming
(0~3)
2
0: From safety on 1: From starting
2: Always 3:Never
3
Active Actions (0~4)
0
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
4
Active Delay (0~20.0)s
2.0
Time from detecting active to confirm
5
Description
LCD display detailed contents when
the input is active.
Remote Start Input
1
Contents
Setting
(0~1)
0
0: Closed to active 1: Open to active
Flexible Input Port 1
1
Contents
Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active 1: Open to active
3
Arming
(0~3)
2
0: From safety on 1: From starting
2: Always 3:Never
4
Active Actions (0~4)
0
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication
5
Active Delay (0~20.0)s
2.0
Time from detecting active to confirm
6
Description
LCD display detailed contents when
the input is active.
Flexible Input Port 2
1
Contents
Setting
(0~50)
0
User defined. See form 3
2
Active Type
(0~1)
0
0: Closed to active 1: Open to active
3
Arming
(0~3)
2
0: From safety on 1: From starting
2: Always 3:Never
4
Active Actions (0~4)
1
0: Warn; 1: Shutdown; 2:Trip and stop
3:Trip 4: Indication