Smartgen HGM8100A User Manual Download Page 49

                                                                         

 

HGM8110A/8120A Genset Controller User Manual                                                                  Page 49 of 57 

8

 

PARAMETER EDITING 

1)

 

Advanced  Parameters  Setting

:  After  controller  start, 

press

and

to  advanced  parameter  password 

confirmation interface (picture on the right). Press “+” and “-” 

to  increase  or  decrease  values  and  input  the  corresponding 

password; press “√” key to right move the bit, in fourth bit press “√” key to check password. If 

password  is  correct,  enter  into  advanced  parameter  setting  interface,  otherwise,  exit  directly. 

(Factory default password is 

00318

 and users can modify it.)   

Press “+” key and “-” key to scroll screen; select parameter you want to configure and press “√” 

key (the parameter will highlight with black), press “+” key or “-” key to change parameter value, 

press “√” key to move the bit, in fourth bit press “√” key to confirm setting.   

2)

 

Basic Parameter Setting:

 After controller start, press 

  for 

more than 3s to enter into Basic Parameter Setting interface; 

The  frequently-used  parameters  can  be  set  via  both  Basic 

Parameter Setting and Advanced Parameter Setting, however, 

set the  frequently-used  parameters via Basic  Parameter  Setting  is  recommended  as  there  are 

lots of parameters in Advanced Parameter Setting and inconvenience. The picture on the right is 

“Basic  Parameter  Setting”  interface,  the  parameter  which  highlight  with  black  is  the  current 

setting one.   

3)

 

Date 

and 

Time 

Setting:

 

After 

controller 

start, 

press

and

to  the  Date  and  Time  Setting  interface 

(picture  on  the right).  The digit  which  highlights  with  black  is 

currently adaptable for user by pressing “+” key and “-” key to 

increase  and  decrease  the  value.  Press  “√”  key  to  confirm  setting  and  the  bit  will  right  move 

automatically.  Number  “6”  in  the  parenthesis  is  the  day  of  the  week.  It  is  set  by  the 

microprocessor based on current date, so the user does not need to modify it. 

CAUTION:

 Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnect 

conditions  selection,  configurable  input,  configurable  output,  various  delay),  otherwise,  shutdown  and  other  abnormal 

conditions may happen. 

Input Password 
 

  0

****

 

 

Basic Parameter Setting 

                     

>Return

 

>Mains Rated Voltage 
>Mains Rated Frequency 
>Crank Disconnect 

Date and Time 
20

1

3.01.26 (6) 15:19:22 

   
 
 

Summary of Contents for HGM8100A

Page 1: ...HGM8100A GENSET CONTROLLER HGM8110A HGM8120A VFD DISPLAY USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...ed to Smartgen Technology at the address above Any reference to trademarked product names used within this publication is owned by their respective companies SmartGen Technology reserves the right to...

Page 3: ...his publication Table 2 Notation Clarification Sign Instruction NOTE Highlights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictl...

Page 4: ...OPERATION 19 4 6 GENSET CONTROLLER ATS CONTROL PROCEDURES 20 4 7 VIEWING EVENT LOG 21 5 PROTECTION 22 5 1 WARNING 22 5 2 SHUTDOWN ALARM 24 5 3 TRIP AND STOP ALARM 26 5 4 TRIP ALARM 26 6 WIRING CONNEC...

Page 5: ...ONNECT SELECTION 48 8 PARAMETER EDITING 49 9 SENSORS SETTING 51 10 COMMISSIONING 52 11 TYPICAL APPLICATION 53 12 INSTALLATION 55 12 1 BATTERY VOLTAGE INPUT 55 12 2 SPEED SENSOR INPUT 55 12 3 OUTPUT AN...

Page 6: ...rference Easy to maintain and upgrade due to the plug in terminal HGM8110A 8120A genset controllers integrate digitization intelligentization and network technology which are used for genset automatio...

Page 7: ...t Suitable for 3 phase 4 wire 3 phase 3 wire single phase 2 wire and 2 phase 3 wire systems with voltage 120 240V and frequency 50 60Hz Collects and shows 3 phase voltage current power parameter and f...

Page 8: ...ture shutdown Low oil pressure alarm Low oil pressure shutdown Over speed shutdown Low fuel level warn Battery voltage high warn Battery voltage low warn Load over current shutdown Fail to start alarm...

Page 9: ...ccumulate the value which make convenience to users to count the total value as their wish Widely power supply range DC 8 35 V suitable to12 24V starting battery voltage environment With international...

Page 10: ...DC28V at supply output Fuel Relay Output 16A DC28V at supply output Aux Output 1 16A DC28V at supply output Aux Output 2 16A DC28V at supply output Aux Output 3 16A DC28V at supply output Aux Output 4...

Page 11: ...rm setting value Event log Pressing this key will view shutdown history records Again pressing this key will exit When there is trip alarm occurs pressing and holding this button for more than 3 secon...

Page 12: ...Alarm Fast flashing 5 times per sec Generator normal light It is light on when generator is normal flashing when generator state is abnormal off when there is no generator power Mains normal light It...

Page 13: ...ne voltage frequency Load including as below Each phase current total active power positive and negative total reactive power positive and negative total apparent power average power factor positive a...

Page 14: ...ervoltage Gen Over Frequency Gen Under Frequency and so on Event log Records all start stop events shutdown alarm trip and stop alarm manual auto start or stop and the real time when alarm occurs Exam...

Page 15: ...ime ETS Solenoid Hold Fail to Stop Delay After Stop Time Example Basic Parameter Setting Return Mains Rated Frequency Form 1 are used for changing the setting contents to enter settings form 2 to exit...

Page 16: ...etting contents to enter settings form 2 to exit setting Generator Generator Setting Return Form 2 are used for changing the setting contents form 3 Select Return and press to return to previous menu...

Page 17: ...form 7 return to previous menu form 4 Sel Disable Set Value 00110 Return Value 00108 Delay 00005 Gen Overvolt Warn Sel Enable Set Value 00000 Return Value 00108 Delay 00005 Form 7 are used for changin...

Page 18: ...alarms and Aux input if configured are disabled As soon as this delay is over start idle delay is initiated if configured 8 During start idle delay under speed under frequency under voltage alarms are...

Page 19: ...iesel genset running controller can protect genset to stop effectively and quickly please refer to No 4 9 of Starting Sequence for more details Under Manual Mode genset on load is decided by whether m...

Page 20: ...rator switch on If transfer fails and warning is Enable there is alarming signal 2 If input port is not configured as Close Auxiliary Mains load is transferred into generator load after switch off and...

Page 21: ...enerator output NOTE When using ATS of no interposition switch off detecting should select Disable When using ATS of having interposition switch off Disable or Enable both are OK If choose Enable swit...

Page 22: ...igher than the set value it will send warn signal 7 Under Voltage Warn When controller detects the voltage is lower than the set value it will send warn signal 8 Over Current Warn When controller dete...

Page 23: ...set value it will send warn signal 24 Level Sensor Open When controller detects the sensor is open circuit and the action selects Warning it will send warn signal 25 Low Level Warn When controller det...

Page 24: ...ltage When controller detects the voltage value is higher than the set value it will send stop signal 8 Under Voltage When controller detects the voltage value is lower than the set value it will send...

Page 25: ...wn it will send stop signal 20 Flexible Sensor 1 High When controller detects the sensor value is higher than the max set value it will send stop signal 21 Flexible Sensor 1 Low When controller detect...

Page 26: ...e power is positive is higher than the set value and the action selects Trip and Stop it will send a trip and stop signal 5 Digital Input Ports When digital input port is set as Trip and Stop and the...

Page 27: ...mmended 3 Emergency stop 2 5 Connected with DC power supply via emergency stop button Also supply power to fuel relay and crank relay Max 30A fuse is recommended 4 Fuel relay output 2 5 DC power is su...

Page 28: ...circuit If not hang it in the air 27 Aux Output 6 Mains Close Relay Output 2 5 Control mains to take load Volts free contactor Rated 16A Also can be set as other function Details see table 13 28 48 2...

Page 29: ...ature sensor 2 1 0 Temperature sensor input can be connected to an external resistance sensor Also can be set as Oil Pressure sensor or Fuel level sensor 44 Oil pressure sensor 1 1 0 Oil pressure sens...

Page 30: ...Disable 1 Enable 7 Over Voltage 0 1000 120 Setting value is mains rated voltage s percentage and return value and delay value can be set 8 Under Voltage 0 1000 80 9 Over Frequency 0 1000 Disable Sett...

Page 31: ...nset stopped and standby Engine Setting 1 Engine Type Fixed value 0 0 Default Conventional unit non ECU 2 Flywheel Teeth 10 300 118 Tooth number of the engine for judging of starter separation conditi...

Page 32: ...s possible 17 Disconnect Generator Freq 0 200 24 When generator frequency higher than the set value starter will be disconnected See the installation instruction 18 Disconnect Engine Speed 0 200 24 Se...

Page 33: ...req Shutdown 0 200 80 12 Over Volt Warn 0 1000 110 Setting value is percentage of generator rated voltage Delay value and return value also can be set 13 Under Volt Warn 0 1000 84 14 Over Freq Warn 0...

Page 34: ...Module Address 1 254 1 Controller s address during remote sensing 3 Stop Bits 0 1 0 0 2 stop bits 1 1 stop bit 4 Language 0 2 0 0 Simplified Chinese 1 English 2 Others 5 Password 0 65535 00318 For ent...

Page 35: ...Open Circuit Action 0 2 0 0 Warn 1 Shutdown 2 No action 3 Low Level Warn 0 300 10 Warn when level lower than this value It is detecting all the time The delay value and return value also can be set F...

Page 36: ...n to active 3 Active Range 0 3 2 0 From safety on 1 From starting 2 Always 3 Never 4 Active Actions 0 4 1 0 Warn 1 Shutdown 2 Trip and stop 3 Trip 4 Indication 5 Active Delay 0 20 0 s 2 0 Time from de...

Page 37: ...ble 13 2 Active Type 0 1 0 0 Normally open 1 Normally close Flexible Output Port 6 1 Contents Setting 0 239 31 Mains closed output See table 13 2 Active Type 0 1 0 0 Normally open 1 Normally close NOT...

Page 38: ...flow to stop the engine as soon as possible 18 Audible Alarm Action when warning shutdown trips Can be connected annunciator externally When Alarm Mute configurable input port is active it can remove...

Page 39: ...idle used for control part of ECU dropping to idle speed temporary reserved 40 Reserved 41 Reserved 42 Pulse Raise Speed Active 0 1s when controller enter into warming up delay used for control part o...

Page 40: ...d Shutdown Action when under speed shuts down 104 Over Speed Warn Action when over speed warn 105 Over Speed Shutdown Action when over speed shutdown alarm 106 Loss of Speed Signal Shutdown Action whe...

Page 41: ...2 Reserved 143 Low OP Warn Action when low oil pressure warning 144 Low OP Shutdown Action when low oil pressure shutdown 145 OP Sensor Open Action when oil pressure sensor is open circuit 146 Reserve...

Page 42: ...2s Output time 3s Condition output contents output port 1 is active Close when condition output active inactive close when active disconnect when inactive Output port 1 active after enter starts time...

Page 43: ...ctive close when active disconnect when inactive Contents of AND condition output S3 output port 3 is active Close when AND condition output S3 is active inactive close when active disconnect when ina...

Page 44: ...amp Test All LED indicators are illuminating when input is active 6 Panel Lock All keys in panel is inactive except and there is in the right of first row in VFD when input is active 7 Reserved 8 Idle...

Page 45: ...ally and take load after normal running when input inactive genset will stop automatically 29 Remote Start Off Load In Auto mode when input is active genset can start automatically and NOT take load a...

Page 46: ...Type Description HGM8120A 47 Alternative Config1 When input is active alternative configuration is active It can set different parameters which makes it easy to select current configuration via input...

Page 47: ...is 0 6K default is SGX sensor 2 Pressure Sensor 0 Not used 1 Custom Res Curve 2 Custom 4 20mA curve 3 VDO 10Bar 4 CURTIS 5 VOLVO EC 6 DATCON 10Bar 7 SGX 8 SGD 9 SGH 10 VDO 5bar 11 15 Reserved Defined...

Page 48: ...or separate with engine immediately and can check crank disconnect exactly 2 Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel teeth 3 When set as speed senso...

Page 49: ...nced Parameter Setting however set the frequently used parameters via Basic Parameter Setting is recommended as there are lots of parameters in Advanced Parameter Setting and inconvenience The picture...

Page 50: ...set value When setting the minimum value the return value must over set value NOTE Please set the generator frequency value as low as possible when cranking in order to make the starter be separated q...

Page 51: ...er can adjust it in curve type 3 When input the sensor curve X value resistor must be input from small to large otherwise mistake occurs 4 If select sensor type as None sensor curve is not working 5 I...

Page 52: ...stop to reset controller 6 Recover the action of stop engine start e g Connect wire of fuel valve press start button again genset will start If everything goes well genset will normal run after idle...

Page 53: ...p output according to user s configuration should not be less than 2 for battery cathode resistance if less than 2 please expand relays with more than 30A current in corresponding output If the engine...

Page 54: ...f 57 Fig 5 3 Phase 3 Wire Connection Diagram take HGM8120A for example Single Phase 2 Wire take HGM8120A for example Fig 6 Single Phase 2 Wire Connection Diagram take HGM8120A for example Fig 7 2 Phas...

Page 55: ...OTE Speed sensor is the magnetic equipment which be installed in starter and for detecting flywheel teeth Its connection wires to controller should apply for 2 cores shielding line The shielding layer...

Page 56: ...ecting and active power maybe not correct NOTE ICOM port must be connected to negative pole of battery WARNING When there is load current transformer s secondary side is prohibited open circuit 12 5 W...

Page 57: ...r crank disconnect Check the oil pressure sensor and its connections High water temp alarm after crank disconnect Check the temperature sensor and its connections Shutdown alarm in running Check relat...

Reviews: