![Smartgen HGM8100A User Manual Download Page 11](http://html1.mh-extra.com/html/smartgen/hgm8100a/hgm8100a_user-manual_1297525011.webp)
HGM8110A/8120A Genset Controller User Manual Page 11 of 57
4
OPERATION
4.1
KEY FUNCTION
Table 4 Key Descriptions
Key
Name
Description
Stop/Reset
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm in stop mode; During stopping
process, press this button again to stop generator immediately.
Start
Start genset in Manual/Test mode.
Manual mode/
Config. ‘
-
’
Pressing this key will set the module into manual mode. In
setting parameter status, press this key will decrease setting
value.
Test mode/
Config. ‘
+
’
Pressing this key will set the module into test mode (only for
HGM8120A). In setting parameter status, press this key will
increase setting value.
Auto mode/Confirm
Pressing this key will set the module into auto mode. In setting
parameter status, press this key will right shift cursor or confirm
setting value.
Event log
Pressing this key will view shutdown history records. Again
pressing this key will exit.
When there is trip alarm occurs, pressing and holding this button
for more than 3 seconds can reset the alarm.
Page Down
Screen scroll in parameters interface or event log interface.
NOTE:
In manual mode, pressing
and
simultaneously will force generator to crank. Successful start
will not be judged according to crank disconnect conditions, operator will have to crank the starter motor manually;
when operator decides that the engine has fired, he/she should release the button and start relay will be deactivated,
safety on delay will start.
NOTE:
Pressing and holding
for more than 3 seconds enters basic parameter configuration menu;
NOTE:
Pressing
and
enters advanced parameter configuration menu;
CAUTION:
Default password is 00318, user can change it in case of others change the advanced parameters setting.
Please clearly remember the password after changing. If you forget it, please contact Smartgen services.