HGM8110A/8120A Genset Controller User Manual Page 21 of 57
failure while switch on outputting. When detecting time out, if switch on failed, it waits for switch on.
Otherwise, switch on is completed.
If transfer failure warning is “Enable”, there is warning signal that “switch on fail”.
2)
If input port is not configured as Closed Auxiliary
Generator un-load is transferred into generator load, close generator output.
Generator load is transferred into generator un-load, open generator output.
NOTE:
When using ATS of no interposition, switch off detecting should select “Disable”;
When using ATS of having interposition, switch off “Disable” or “Enable” both are OK. If choose “Enable”, switch off output
should be configured;
When using AC contactor, switch off “Enable” is recommended.
4.7
VIEWING EVENT LOG
On the control panel, press
key to view previous running records of the controller, including all
start/stop records (shutdown, trip and stop, manual/auto start/stop) and corresponding time. Press
key to view records backward. Again press
key to return real time display status of the
controller.
HGM8100A
controller can save recent 99-piece event log records.