7.4
SELECTION OF SENSORS
Table 15 Sensors Selection
No.
Description
Remark
1
Temperature Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
5 VOLVO-EC
6 DATCON
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
Defined
resistance’s
range is 0~6KΩ, default
is SGX sensor.
2
Pressure Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS
5 VOLVO-EC
6 DATCON 10Bar
7 SGX
8 SGD
9 SGH
10 VDO 5bar
11~15 Reserved
Defined
resistance’s
range is 0~6KΩ, default
is SGX sensor.
3
Fuel Level Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 SGD
4 SGH
5~15 Reserved
Defined
resistance’s
range is 0~6KΩ, default
is SGH sensor.
NOTE:
User should make special declare when order controller if your genset equipped with sensor of 4~20mA.