No.
Items
Parameters
Defaults
Description
1
Contents
Setting
(0~239)
48
Common alarm. See table 13.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Flexible Output Port 3
1
Contents
Setting
(0~239)
38
ETS solenoid hold. See table 13.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Flexible Output Port 4
1
Contents
Setting
(0~239)
35
Idle speed control. See table 13.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Flexible Output Port 5
1
Contents
Setting
(0~239)
29
Generator closed output. See table 13.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Flexible Output Port 6
1
Contents
Setting
(0~239)
31
Mains closed output. See table 13.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
NOTE:
Overcurrent setting details about definite time delay and inverse definite minimum time are as follows:
Definite Time
:
Overcurrent delay is definite time delay. Different overcurrent value has corresponding delay.
Inverse Definite Minimum Time(IDMT)
:
Overcurrent delay decrease with the increase of overcurrent. Different
overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)
2
T: Overcurrent delay (second)
T: Timing multiplier ratio
IA: Current max. load current (L1/L2/L3)
IT: Overcurrent setting value
Example:
t = 36
IA = 550A
IT =500A
Conclusion: T = 3600s (1 hour)