HGM8110A/8120A Genset Controller User Manual Page 44 of 57
7.3
DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS 1-6
Table 14 Defined Contents of Configurable Input Ports (All GND Connected (B-) Active)
No.
Type
Description
0
Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shuts down
after high-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
1
Reserved
2
Alarm Mute
Can prohibit “Audible Alarm” output when input is active.
3
Reset Alarm
Can reset shutdown alarm and trip alarm when input is
active.
4
60Hz Active
Use for CANBUS engine and it is 60Hz when input is
active.
5
Lamp Test
All LED indicators are illuminating when input is active.
6
Panel Lock
All keys in panel is inactive except
and there is
in the right of first row in VFD when input is active.
7
Reserved
8
Idle Control Mode
Under voltage/frequency/speed protection is inactive.
9
Inhibit Auto Stop
In
Auto
mode, during generator normal running, when
input is active, inhibit generator stop automatically.
10
Inhibit Auto Start
In
Auto
mode, inhibit generator start automatically when
input is active.
11
Inhibit Scheduled Start
In
Auto
mode, inhibit scheduled run genset when input is
active.
12
Reserved
13
Aux Gen Closed
Connect generator loading switch’s Aux. point.
14
Inhibit Gen Load
Prohibit genset switch on when input is active.
15
Aux Mains Closed
Connect mains loading switch’s Aux. point.
16
Inhibit Mains Load
Prohibit mains switch on when input is active.
17
Auto Mode Lock
When input is active, controller enters into Auto mode; all
the keys except
are inactive, and will show in
the right of first line of VFD display.
18
Auto Mode Invalid
When input is active, controller won’t work under Auto