HGM6100U Series Automatic Control Module
HGM6100U Automatic Genset Controller ISSUE 2014-10-28 Version 1.2 Page 6 of 39
Temp. (WT), °C/ °F both are displayed
Oil pressure (OP), kPa/Psi/Bar are all displayed
Fuel level (FL), %
Speed (SPD), RPM
Battery Voltage (VB), V
Charger Voltage (VD), V
Hours counter (HC) can accumulate Max. 999999 hours.
Start times can accumulate Max.999999 times.
Control protection: Automatic start/stop of genset, load transfer(ATS control) and
perfect failure display and protection;
With ETS, idle speed control, pre-heat control, speed droop/raising control, all of
them are relay output;
Parameter setting: Allow user to modify setting and store them in internal FLASH
memory. The parameters cannot be lost even when power off. All of parameters can
be set not only from the front panel, but also use programmable interface (or PS485
interface) to adjust them via PC.;
Multi sensors of temperature, pressure and fuel level can be used directly,
parameters can be defined by user;
Multi conditions of crank disconnect (speed sensor, oil pressure, generator) can be
selected;
Power supply range: (8~35)VDC, accommodating to different starting battery volts;
All parameters use digital modulation, instead of analog modulation using
conventional potentiometer, having improved reliability and stability;
Add rubber gasket between shell and controller screen, the waterproof can reach
IP55;
Controller is fixed by metal fixing clips;
Modular design, flame-retardant ABS shell, embedded mounting, compact structure
and easy installation.